User manual
SmartBox
®
 1 / SmartBox
®
 2 / SmartBox
®
 3 
12 / 16  Part No. 28 100 57 e 
Menu 
Setting 
Description 
13.Rounding 
Automatically 
Without rounding 
20L 
50L 
100L 
200L 
500L 
1.000L 
Default settings 
minimal increments 
Rounding increments in relation to the set volume 
set with [+] / [-] keys 
14.–17.Exit 
Press [Enter] to return to display mode 
18.Language 
Language: 
German, English, French   [+] / [-] / [Enter] 
Names: 
ESC                                [+] / [-] / [Enter] 
Name Tank 1: Suggested name 
Letters can be changed with       [+] / [-] / [Enter] 
19.Exit 
Press [Enter] to return to display mode 
20.LCD 
display 
Contrast: 24 
Set the contrast of the LCD display 
21.Device 
info 
Displays information about 
Software version:   V4.00 (e. g.) 
Serial number: Tank 1: SN=1234 (e. g.) 
Offset + Gain:   X0 = 4.05 mA; B = 
1268 (Tank 1) 
22.Test 
current 
Test function for the current mA value of the 
measurement probe: ADC = 28A0 = 04.00 mA 
If level probe is not submerged, the value should 
be close to 4 mA. Tolerance range is 3.7...4.3 
mA. For larger deviations, see menu item 9. 
23.Test 
relay 
SBox 2+3 
Rel1 ON / OFF 
Relay test 
24.Reset 
ESC 
Reset the device software: 
Exit this function without executing it. 
Restart 
Initialisation. The device software restarts and 
keeps all device settings. 
Factory settings 
Complete reset of all parameters to the original 
delivery status. 
26.Exit 
Press [Enter] to return to display mode 