MR-2100/2200 Fire Alarm Control Unit INSTALLATION MANUAL Revision 1 Document #: LT-2000 WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be read carefully.
MR-2100/MR-2200 Installation Manual Contents 1.0 Technical Information .............................................................................................................................. 1 1.1 Introduction .................................................................................................................................... 1 1.2 Features ......................................................................................................................................... 1 1.
MR-2100/MR-2200 Installation Manual List of Tables & Figures Table 1: AC Input ................................................................................................................................. 8 Table 2: Battery Power ........................................................................................................................ 8 Table 3: Addressable Input (Signaling Line Circuit) .............................................................................
MR-2100/MR-2200 Installation Manual 1.0 Technical Information 1.1 Introduction The MR-2100/MR-2200 Fire Alarm Control Panel (FACP) is the heart of a sophisticated microprocessor based fire detection system. Meeting the demands of economy and capability, these modular panel offer support for one or two loops of up to 198 devices on each loop. Optional modules mount directly to the chassis. Modules are available that provide additional NAC output circuits, function relay output circuits, annunciation, etc.
MR-2100/MR-2200 Installation Manual 1.
MR-2100/MR-2200 Installation Manual 1.7 System Components Basic System A basic system consists of the Back Box, Main Board, Display Board and one transformer. Canadian versions also include an Eight Zone LED Module. Back Box The enclosure includes the back box, outer door, dead front door and hardware plate. It can be flush or surface mounted without requiring additional hardware. Both the outer door and dead front doors are quickly removable using pin-hinges.
MR-2100/MR-2200 Installation Manual Display Board The Display Board provides LED and LCD status annunciation, hotkeys, and keypads for message retrieval and programming. A replacement Display can be ordered under RB-MR-2201. Optional (Internal) Components NAC Expander Board - MRNC2 The NAC Expander Board provides two additional NAC output circuits. A ribbon cable connects this module. Any combination of NAC and Relay expanders can be added (to a maximum of three modules total) within the basic enclosure.
MR-2100/MR-2200 Installation Manual DACT Module - MRDL The optional Digital Alarm Communicator Transmitter (DACT) module is added to the system to provide Remote Station monitoring of system alarm, trouble, and supervisory conditions. Use of the DACT module requires that two telephone lines be provided for connection to the DACT. Service must be arranged with a Central Station monitoring facility for Remote Station Service. Refer to the MRDL Installation Instructions for more information.
MR-2100/MR-2200 Installation Manual MR22NTWR12 The MR22NTWR12 provides the network interface between the MR-2200 and the rest of the control units on a peer-to-peer network. This module plugs directly into the MR-2200 main board. The MR22NTWR12 version features Port 1 and Port as both RS232. Reverse Polarity Municipal Box - MRCTYB The optional MRCTYB can be configured for remote Station (reverse polarity) or Municipal Master (local energy) service.
MR-2100/MR-2200 Installation Manual MR-2900 The MR-2900 is a networkable fire alarm panel with both addressable and conventional input capability. Refer to the MR-2900/MR-2920 Fire Alarm Control Unit Installation Manual. MR-2944 The MR-2944 is a network annunciator with Liquid Crystal Display and/or LED Zone display, general system status lights, and general function keys. Refer to the MR-2944 Annunciator Unit Installation Manual. Note: Not to be used for ULC applications.
MR-2100/MR-2200 Installation Manual 2.0 Technical Specifications 2.1 Electrical Specifications Table 1: AC Input Circuit / Model / Item Rating Standard Primary AC Input 1 MR2100R, MR2200R 120V, 60Hz, 1.03 A maximum 240V, 50Hz, 0.51A maximum Optional Primary AC Input 2 MR2100R, MR2200R 120V, 60Hz, 2.5 A maximum 240V, 50Hz, 1.26A maximum Table 2: Battery Power (Use sealed lead acid batteries only!) Circuit / Model / Item Rating Battery Charger Current limited float charger Float charge: 27.
MR-2100/MR-2200 Installation Manual Table 3: Addressable Input (Signaling Line Circuit) Circuit / Model / Item Rating Voltage 24Vdc nominal, 27.5Vdc maximum Maximum loop length Refer to “3.
MR-2100/MR-2200 Installation Manual Table 7: Communications Ports Port Rating COM1, COM2 (Secutron MR peerto-peer network, redundant DCLR) 10km (33,000 feet) maximum distance between nodes, minimum 28 AWG wires. Programmable baud rate with up to 200 panels at 1200 bps, 254 panels at 2400, 4800, and 9600 bps.
MR-2100/MR-2200 Installation Manual 3.0 Installation 3.
MR-2100/MR-2200 Installation Manual Replacing the Outer Door 1. Unlock the Door with the key provided. 2. Detach the grounding strap (Qty: 2) from the backbox by removing the #6 flange nuts (Qty: 2) that are attached to the studs on the backbox. Reattach the #6 flange nuts (Qty: 2) to the studs to prevent them from getting lost or discarded. 3. Open the Door to approximately 135o and lift up to remove the outer door from the backbox, store door in a safe place. Removing the MR-2100/MR-2200 Electronics A.
MR-2100/MR-2200 Installation Manual 14-1/2" (368 mm) 7/8" (23 mm) lip each side 3/4" (19 mm) lip top and bottom 16-1/8" (410 mm) 5-1/2" (140 mm) 3" (76 mm) 1-1/4" (32 mm) 21-3/4" (552 mm) 26-1/2" (673 mm) 29" (740 mm) 27-1/2" (699 mm) 8-1/2" (216 mm) Battery shelf Figure 1: Knockouts and Mounting Holes 13
MR-2100/MR-2200 Installation Manual 3.3 Internal Assembly • Attach AC wiring to the AC Terminal Block (see Figure 4 on page 16). Attach green ground wire to ground screw on backplate. Notes: • Do not apply power to the unit until all doors, cables and wiring are installed and inspected. • This AC circuit must be a separately fused 20A dedicated circuit. It is recommended that the breaker be locked in the OFF position during installation.
MR-2100/MR-2200 Installation Manual Minimum 1/4” separation from Reverse Polarity or Master Box (MRCTYB) wiring to all power limited wiring. Area to right of bold line is NOT power limited. MRCTYB Communications harness is routed under MRCTYB PCB and white plastic from location circled on MRCTYB to location circled on main PCB.
MR-2100/MR-2200 Installation Manual 3.4 Wiring Power Connections " RIDGE 2%$ "ATT ",+ "ATT " ! " ! " RIDGE ! . !# " ! . !# " The Main Control Unit requires an AC power supply. This supply is connected as shown below: 4O "ATTERIES 4O "RIDGE 2%$ / 2 !.' % 2%$ 3 ) ,6 % 2 !# 4" 0RIMARY %!24( ",5% -!). 0/7%2 8&-2 0RIMARY 2%$ ",5% !58 %80!.3)/. 8&-2 2%$ (/4 (/4 6 6 "2)$'% 2%#4)&)%2 ",5% .%54 !# 4%2-).!, ",/#+ !# 3ECONDARY ",+ 2%$ 3ECONDARY 9%, ",+ 2%$ 9%, '.
MR-2100/MR-2200 Installation Manual The internal batteries are not used when an external battery box is used. The wires for connecting the power supply board to the batteries are supplied with the panel if a battery box is ordered at the same time. Warning: Never connect or disconnect the batteries while the AC power is off.
MR-2100/MR-2200 Installation Manual Addressable Circuit Connections Addressable Class B (Style 4) Circuit This is a 2-wire supervised Class B (Style 4) communications circuit using addressable devices. Wire capacitance and resistance will affect the allowable wire length. The recommended wiring is twisted unshielded pair. Consult Secutron's Applications Department for specific requirements. Maximum wire lengths are up to 10,000 ft (see Appendix). Devices will be connected as indicated in the diagram below.
MR-2100/MR-2200 Installation Manual Notification Appliance Circuit Connections Class B (Style Y) NAC This is a 2-wire Class B (Style Y) supervised signaling (notification appliance) circuit. Devices and the 10k ohm end-of-line resister will be connected as indicated in the figure below. Maximum wire lengths are shown in the Appendix. Use only approved devices.
MR-2100/MR-2200 Installation Manual EVAX System Wiring Conduit 20’ Max GND MV2700 2700MM MV GND TX RX TS3 TX RX RS232-2 MR-2100/2200 MR-2100 / MR-2200 Main Board 3.5 Maximum Wiring Length for Addressable Circuits Gauge Belden No. Maximum Distance 18 9571 975m (3200 ft) 16 9572 1400m (4600 ft) 14 9580 2435m (8000 ft) 12 9582 3045m (10000 ft) Note: Distances noted in this table account for the total length of wire, from the panel to furthest device and back to the panel. 3.
MR-2100/MR-2200 Installation Manual 4.
MR-2100/MR-2200 Installation Manual 5.0 Appendix B: Battery Calculations & Compatible Batteries 5.1 Battery Calculation Worksheet 1. Enter the number of each installed module type in the ’Quantity’ column next to the appropriate module description. 2. For each quantity entry, multiply the value in the ’Quantity’ column by the value in the ’Standby’ column and enter the value in the ’Total Standby’ column. 3.
MR-2100/MR-2200 Installation Manual Device Standby Total Alarm Total Qty.
MR-2100/MR-2200 Installation Manual 5.2 Battery Selection Calculations 1. From previous calculations, locate total Standby Current (A) and convert to amperes. A = ________ (Note: amperes = mA ÷ 1000; µA ÷ 1,000,000; examples: 250 mA = 0.25 A; 1500 µA = 0.0015 A) 2. Identify Standby Time (C), in hours. C = ______ (typically 4, 24, 48, or 60 hr) 3. From previous calculations, locate total Alarm Current (B) in amperes. B = ______ 4. Identify Alarm Time (D) in minutes.
MR-2100/MR-2200 Installation Manual 6.
MR-2100/MR-2200 Installation Manual 7.0 Warranty & Warning Information Warning Please Read Carefully Note to End Users: This equipment is subject to terms and conditions of sale as follows: Note to Installers This warning contains vital information. As the only individual in contact with system users, it is your responsibility to bring each item in this warning to the attention of the users of this system.
MR-2100/MR-2200 Installation Manual breakdowns, interruptions, loss, destruction, alteration or other problems in the use of a product arising our of, or caused by, the software. Every fire is different in the amount and rate at which smoke and heat are generated. Smoke detectors cannot sense all types of fires equally well.
MR-2100/MR-2200 Installation Manual Limited Warranty Secutron Inc. warrants the original purchaser that for a period of two years from the date of manufacture, the product shall be free of defects in materials and workmanship under normal use. During the warranty period, Secutron Inc. shall, at its option, repair or replace any defective product upon return of the product to its factory, at no charge for labor and materials.
MR-2100/MR-2200 Installation Manual Out of Warranty Repairs Secutron Inc. will at its option repair or replace out-of-warranty products which are returned to its factory according to the following conditions. Anyone returning goods to Secutron Inc. must first obtain an authorization number. Secutron Inc. will not accept any shipment whatsoever for which prior authorization has not been obtained. Products which Secutron Inc. determines to be repairable will be repaired and returned.
© 2007 Secutron, Inc. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form by any means electronic, magnetic, optical, chemical, manual, or otherwise without the prior consent of Secutron. Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: (888) SECUTRON (888) 732-8876 Fax: (905) 660-4113 U.S.