Unit installation

MR-2100/MR-2200 Installation Manual
10
Table 7: Communications Ports
Table 8: Environmental Specifications
Port Rating
COM1, COM2 (Secutron MR peer-
to-peer network, redundant DCLR)
10km (33,000 feet) maximum distance
between nodes, minimum 28 AWG wires. Pro-
grammable baud rate with up to 200 panels at
1200 bps, 254 panels at 2400, 4800, and 9600
bps.
ANN (annunciator port) Fixed baud rate 4800bps;(see MR-2644
instructions for wiring distances)
CON4 (Dialer/City Module Port) Fixed baud rate 4800bps
J1 (Service and serial printer port) Fixed baud rate 9600bps; 6m (20ft)
maximum distance
Condition Rating
Operating Temperature 0ºC – 49ºC / 32ºF – 120ºF
Humidity 93% RH non-condensing