Unit installation
MR-2100/MR-2200 Installation Manual
20
EVAX System Wiring
3.5 Maximum Wiring Length for Addressable Circuits
Note: Distances noted in this table account for the total length of wire, from the panel to furthest device
and back to the panel.
3.6 Maximum Wiring Length for Bell Circuits
Note: Distances noted in this table account for the total length of wire, from the panel to furthest device and
back to the panel.
Gauge Belden No. Maximum Distance
18 9571 975m (3200 ft)
16 9572 1400m (4600 ft)
14 9580 2435m (8000 ft)
12 9582 3045m (10000 ft)
12AWG 14AWG 16AWG 18AWG
Max R Max I m ft m ft m ft m ft
8.00 0.25 768 2519 483 1584 304 996 191 627
4.00 0.5 384 1259 241 792 152 498 95 313
2.67 0.75 256 840 161 528 101 332 64 209
2.00 1 192 630 121 396 76 249 48 157
1.60 1.25 154 504 97 317 61 199 38 125
1.33 1.5 128 420 80 264 51 166 32 104
1.14 1.75 110 360 69 226 43 142 27 90
1.00 2 96 315 60 198 38 125 24 78