Installing the Drive
650 Series AC Drive
Using Cage Clamp Terminals
Strip wire insulation to 5-6mm (0.20-0.24 inches), or alternatively
use wire-crimps. Use a flat-bladed screwdriver, maximum blade size
3.5mm. The cage provides the correct force for a secure connection.
IMPORTANT:
DO NOT lever or turn the screwdriver.
Terminal Block Acceptance Sizes
Wire sizes should be chosen with respect to the operating conditions and your local National
Electrical Safety Installation Requirements. Local wiring regulations always take precedence.
Frame Size
Frame SizeFrame Size
Frame Size Power Terminals
Power TerminalsPower Terminals
Power Terminals
(maximum wire size)
(maximum wire size)(maximum wire size)
(maximum wire size)
Brake Terminals
Brake TerminalsBrake Terminals
Brake Terminals
(maximum wire size)
(maximum wire size)(maximum wire size)
(maximum wire size)
Thermistor/Control
Thermistor/ControlThermistor/Control
Thermistor/Control
Terminals
TerminalsTerminals
Terminals
(maximum wire size)
(maximum wire size)(maximum wire size)
(maximum wire size)
Frame 1 2.5mm
2
/12 AWG Not Applicable 2.5mm
2
/12 AWG
Frame 2
200V
2.5mm
2
/12 AWG Not Applicable 2.5mm
2
/12 AWG
Frame 2
400V
2.5mm
2
/12 AWG 2.5mm
2
/12 AWG 2.5mm
2
/12 AWG
Frame 3
200V & 400V
6.0mm
2
/10 AWG 6.0mm
2
/10 AWG 2.5mm
2
/12 AWG
Power Wiring
Note:
For specified EMC emission and immunity performance, install to EMC Installation
Instructions. Refer to Chapter 10: “Certification for the Drive” - for more information
Protect the incoming mains supply using the specified fuse, or RCD circuit breaker Type B.
IMPORTANT:
We do not recommend the use of circuit breakers (e.g. RCD, ELCB, GFCI), however,
where their use is mandatory, they must:
•
Operate correctly with dc and ac protective earth currents (i.e. type B RCDs as in
Amendment 2 of IEC755).
•
Have adjustable trip amplitude and time characteristics to prevent nuisance tripping
on switch-on.
Control Wiring
Control wiring of between 0.08mm
2
(28AWG) and 2.5mm
2
(12AWG) can be used. Ensure all
wiring is rated for the highest system voltage. All control terminals are SELV, i.e. double-
insulated from power circuits.