Product manual
6-1
Programming Your Application
650 Series AC Drive
1
P
ROGRAMMING
Y
OUR
A
PPLICATION
You can program the drive to your specific application. This programming simply involves
changing parameter values. Access the parameters using the keypad.
For instance, parameter
P
1 selects various Applications which can be used as starting points for
application-specific programming. Each Application internally re-wires the drive for a different
use when it is loaded. The default for the parameter is "1". Changing this parameter's setting to
"2" will load Application 2. Refer to Chapter 12: “Applications” for further information.
If necessary, there are three parameters for tuning your drive. Refer to PID, page 6-6.
Saving Your Modifications
When parameter values are modified or an Application is loaded, the new settings are saved
automatically. The drive will retain the new settings during power-down.
Configurable Parameters
Display
DisplayDisplay
Display Parameter
ParameterParameter
Parameter Description
DescriptionDescription
Description Range
RangeRange
Range Default
DefaultDefault
Default
SET::PAR Menu
SET::PAR MenuSET::PAR Menu
SET::PAR Menu
APPLICATION Selects the Applicaton to be used
(Application 0 does not control a motor)
Application 1: Basic Speed Control
Application 2: Manual/Auto
Application 3: Presets
Application 4: Raise/Lower
Application 5: PI Control
Note:
Parameter values are changed to
factory settings by loading a new
Application, except Motor-Specific
parameters
P
2,
P
6,
P
7 and
P
8.
0= APPLICATION 0
1= APPLICATION 1
2= APPLICATION 2
3= APPLICATION 3
4= APPLICATION 4
5= APPLICATION 5
1
MAX SPEED The frequency at which the 650 will run when
maximum setpoint is applied. The default is
Product Code dependent
7.5 to 240.0Hz 50.0Hz or
60.0Hz
MIN SPEED The minimum frequency at which the 650 will run,
as a percentage of the MAX SPEED parameter
-100.0 to 100.0% 0.0%
ACCEL TIME The time taken for the 650 output frequency to
ramp up from zero to MAX SPEED
0.0 to 3000.0s 10.0s
DECEL TIME The time taken for the 650 output frequency to
ramp down from MAX SPEED to zero
0.0 to 3000.0s 10.0s
MOTOR
CURRENT
This parameter contains the motor nameplate full-
load line current
Product
code
dependent
product
code
dependent
BASE
FREQUENCY
The output frequency at which maximum voltage is
reached. The default is Product Code dependent
25.0 to 240.0Hz 50.0Hz or
60.0Hz
JOG SETPOINT Speed the 650 will run at if the Jog input is high,
as a percentage of the MAX SPEED parameter
-100.0 to 100.0% 10.0%
RUN STOP MODE RAMP : The motor speed is reduced to zero at a
rate set by DECEL TIME (
P
5). A 2 second DC pulse
is applied at end of ramp
COAST : The motor is allowed to freewheel to a
standstill
INJECTION : On a stop command, the motor volts
are rapidly reduced at constant frequency to deflux
the motor. A low frequency braking current is then
applied until the motor speed is almost zero. This
is followed by a timed DC pulse to hold the motor
shaft.
0=RAMP
1=COAST
2=INJECTION
0