Product manual

6-5
Programming Your Application
650 Series AC Drive
Display
DisplayDisplay
Display Parameter
ParameterParameter
Parameter Description
DescriptionDescription
Description Range
RangeRange
Range Default
DefaultDefault
Default
SET::TRIP Menu
SET::TRIP MenuSET::TRIP Menu
SET::TRIP Menu
DISABLE LOOP Disables LOST I LOOP trip (4-20mA) 0= TRIP ENABLED
1= TRIP DISABLED
1
DISABLE STALL Disables STALL trip As
S
LOOP 0
DISABLE MOTOR
OVERTEMP
Disables the motor thermistor trip As
S
LOOP 0
DC LINK RIPPLE
F
Disables the DC link ripple trip As
S
LOOP 0
SET::SETP Menu
SET::SETP MenuSET::SETP Menu
SET::SETP Menu
JOG ACCEL TIME As
P
4, for Jog 0.0 to 3000.0s 1.0
JOG DECEL TIME As
P
5, for Jog 0.0 to 3000.0s 1.0
RAMP TYPE
F
Selects the ramp type 0=LINEAR
1=S
0
S RAMP JERK
F
Rate of change of acceleration of the curve in units
per second³
0.01 to 100.00 s^3 10.00
S RAMP
CONTINUOUS
F
When TRUE and the S ramp is selected, forces a
smooth transition if the speed setpoint is changed
when ramping. The curve is controlled by the S
RAMP JERK parameter. When FALSE, there is an
immediate transition from the old curve to the new
curve
0=FALSE
1=TRUE
1
SKIP FREQUENCY
1
F
This parameter contains the centre frequency of
skip band 1 in Hz
0.0 to 240.0 Hz 0.0
SKIP FREQUENCY
BAND 1
F
The width of skip band 1 in Hz 0.0 to 60.0 Hz 0.0
SKIP FREQUENCY
2
F
This parameter contains the centre frequency of
skip band 2 in Hz
0.0 to 240.0 Hz 0.0
SKIP FREQUENCY
BAND 2
F
The width of skip band 2 in Hz 0.0 to 60.0 Hz 0.0
AUTO RESTART
ATTEMPTS
F
Determines the number of restarts that will be
permitted before requiring an external fault reset
0 to 10 0
AUTO RESTART
DELAY
F
Determines the delay between restart attempts for
a trip included in AUTO RESTART TRIGGERS and
AUTO RESTART TRIGGERS+. The delay is
measured from all error conditions clearing
0.0 to 600.0 s 10.0
AUTO RESTART
TRIGGERS
F
Allows Auto Restart to be enabled for a selection
of trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF 0x0000
AUTO RESTART
TRIGGERS+
F
Allows Auto Restart to be enabled for a selection
of trip conditions.
Refer to Chapter 7: "Trips and Fault Finding" -
Hexadecimal Representation of Trips
0x0000 to 0xFFFF 0x0000
APPLICATION
LOCK
F
Setting this parameter to TRUE prevents editing of
parameter
P
1.
Set this parameter to FALSE to edit parameter
P
1.
0=FALSE
1=TRUE
0
MENU DETAIL Selects FULL or PARTIAL menu detail. The
additional parameters in the FULL menus are
indicated in this table by
F
0=PARTIAL
1=FULL
0