Product manual

6-9
Programming Your Application
650 Series AC Drive
Product-Related Default Values
Frequency Dependent Parameters
The values in the table below are set by changing the "default frequency" parameter. To do this,
power-down the drive. Power-up the drive holding down the STOP and DOWN keys. Release
the keys to display the
e
0.01 parameter.
Caution
You are now in a menu containing some sensitive and important parameters.
Press the UP key to display the
e
0.02 parameter. Press the M key. The values for this parameter
are: 0 = 50Hz default, 1 = 60Hz default. Select the setting using the UP/DOWN keys and then
press the E key. Power-down the drive and power-up again holding down the UP and DOWN
keys. This resets
ALL
parameters to their correct default values.
50Hz default
50Hz default50Hz default
50Hz default 60Hz default
60Hz default60Hz default
60Hz default
MAX SPEED
50 60
BASE FREQUENCY 50 60
Power Dependent Parameters
These parameters are set to a value depending on the overall “power-build” of the drive
indicated by the Product Code, and described here by parameters CL15 and CL12, blocks 2 & 3
of the Product Code.
We recommend that you do not change the Product Code.
650 Model
650 Model650 Model
650 Model Default
DefaultDefault
Default
Frame 1 : 0.25kW 230V
Frame 1 : 0.37kW 230V
Frame 1 : 0.55kW 230V
Frame 1 : 0.75kW 230V
1.5A
2.2A
3.0A
4.0A
Frame 2 : 1.1kW 230V
Frame 2 : 1.5kW 230V
5.5A
7.0A
Frame 2 : 0.37kW 400V
Frame 2 : 0.55kW 400V
Frame 2 : 0.75kW 400V
Frame 2 : 1.1kW 400V
Frame 2 : 1.5kW 400V
Frame 2 : 2.2kW 400V
1.5A
2.0A
2.5A
3.5A
4.5A
5.5A
MOTOR CURRENT
Frame 3 : 2.2kW 230V
Frame 3 : 3.0kW 230V
Frame 3 : 4.0kW 230V
13.0A
18.0A
23.0A
Frame 3 : 3.0kW 400V
Frame 3 : 4.0kW 400V
Frame 3 : 5.5kW 400V
Frame 3 : 7.5kW 400V
6.8A
9.0A
12.0A
16.0A