Product manual

9-5
Technical Specifications
650 Series AC Drive
Analog Inputs/Outputs
Terminals AIN1, AIN2, AOUT1.
Inputs
InputsInputs
Inputs Output
OutputOutput
Output
Range
RangeRange
Range 0-10V and 0-5V (no sign) set via parameter
S
IP13 (AIN1)
0-10V, 0-5V, 0-20mA or 4-20mA (no sign) set via
parameter
S
IP23 (AIN2)
Absolute maximum input current 25mA in current mode
Absolute maximum input voltage 24V dc in voltage mode
0-10V (no sign)
Maximum rated output
current 10mA, with short
circuit protection
Impedance
ImpedanceImpedance
Impedance
Voltage input 20k
Current Input <6V @ 20mA
Resolution
ResolutionResolution
Resolution 10 bits (1 in 1024) 10 bits (1 in 1024)
Dynamic Response
Dynamic ResponseDynamic Response
Dynamic Response Sampled every 10ms Bandwidth 15Hz
Digital Inputs
Terminals DIN1, DIN2, DIN3, DIN4.
Operating Range
Operating RangeOperating Range
Operating Range 0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
IEC1131
undefined state
15V
5V
0V
24V
ON
OFF
Input Current
Input CurrentInput Current
Input Current 7.5mA @ 24V
Sample Interval
Sample IntervalSample Interval
Sample Interval 10ms
Digital Outputs
Terminals DOUT2 (DOUT1 is reserved for future models).
Nominal Open Circuit Output Voltage
Nominal Open Circuit Output VoltageNominal Open Circuit Output Voltage
Nominal Open Circuit Output Voltage 23V (minimum 19V)
Nominal Output Impedance
Nominal Output ImpedanceNominal Output Impedance
Nominal Output Impedance
33
Rated Output Current
Rated Output CurrentRated Output Current
Rated Output Current 50mA
Cabling Requirements for EMC Compliance
Power Supply Cable
Power Supply CablePower Supply Cable
Power Supply Cable Motor Cable
Motor CableMotor Cable
Motor Cable Brake Resistor Cable
Brake Resistor CableBrake Resistor Cable
Brake Resistor Cable Signal/Control Cable
Signal/Control CableSignal/Control Cable
Signal/Control Cable
Cable Type
Cable TypeCable Type
Cable Type
(for EMC Compliance)
(for EMC Compliance)(for EMC Compliance)
(for EMC Compliance)
Unscreened Screened/armoured Screened/armoured Screened
Segregation
SegregationSegregation
Segregation
From all other wiring
(clean)
From all other wiring (noisy)
From all other wiring
(sensitive)
Length Limitations
Length LimitationsLength Limitations
Length Limitations
With Internal AC Supply
With Internal AC SupplyWith Internal AC Supply
With Internal AC Supply
EMC Filter
EMC FilterEMC Filter
EMC Filter
Unlimited *25 metres
25 metres 25 metres
Length Limitations
Length LimitationsLength Limitations
Length Limitations
Without Internal AC
Without Internal ACWithout Internal AC
Without Internal AC
Supply EMC Filter
Supply EMC FilterSupply EMC Filter
Supply EMC Filter
Unlimited 25 metres 25 metres 25 metres
Screen to Earth
Screen to EarthScreen to Earth
Screen to Earth
Connection
ConnectionConnection
Connection
Both ends Both ends Drive end only
Output Choke
Output ChokeOutput Choke
Output Choke
300 metres
maximum
* Maximum motor cable length under any circumstances