Product manual

Certification for the Drive
10-2
650 Series AC Drive
Terminal Tightening Torque
Refer to Chapter 3: “Installing the Drive” – Terminal Tightening Torque.
Terminal/Wire Sizes
North American wire sizes (AWG) are based on NEC/NFPA-70 for ampacities of thermoplastic-
insulated (75ºC) copper conductors.
Power input and output wire sizes should allow for an ampacity of 125% of the rated input and
output amperes for motor branch-circuit conductors as specified in NEC/NFPA-70. Refer to
Chapter 3: “Installing the Drive” – Terminal Block Acceptance Sizes.
Input Fuse Ratings
If fitted, fuses should be in accordance with NEC/NFPA-70.
FRAME 1 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Input Current @ 5kAInput Current @ 5kA
Input Current @ 5kADrive Power
Drive PowerDrive Power
Drive Power
(kW/hp)
(kW/hp)(kW/hp)
(kW/hp)
(A)
(A)(A)
(A)
Supply Fuse Rating (A)
Supply Fuse Rating (A)Supply Fuse Rating (A)
Supply Fuse Rating (A)
10 x 38mm
10 x 38mm10 x 38mm
10 x 38mm
0.25/0.3 4.2 10
0.37/0.5 6.2 10
0.55/0.75 7.9 10
0.75/1.0 10.5 15
FRAME 2 : 1-Phase (IT/TN), 230V
Input Current @ 5kA
Input Current @ 5kAInput Current @ 5kA
Input Current @ 5kADrive Power
Drive PowerDrive Power
Drive Power
(kW/hp)
(kW/hp)(kW/hp)
(kW/hp)
(A)
(A)(A)
(A)
Supply Fuse Rating (A)
Supply Fuse Rating (A)Supply Fuse Rating (A)
Supply Fuse Rating (A)
10 x 38mm
10 x 38mm10 x 38mm
10 x 38mm
1.1/1.5 13.8 20
1.5/2.0 16.0 20
FRAME 2 : 3-Phase (IT/TN), 400V
Drive Power
Drive PowerDrive Power
Drive Power
(kW/hp)
(kW/hp)(kW/hp)
(kW/hp)
Input Current @ 10kA
Input Current @ 10kAInput Current @ 10kA
Input Current @ 10kA
(A)
(A)(A)
(A)
Supply Fuse Rating (A)
Supply Fuse Rating (A)Supply Fuse Rating (A)
Supply Fuse Rating (A)
10 x 38mm
10 x 38mm10 x 38mm
10 x 38mm
0.37/0.5 2.5 10
0.55/0.75 3.3 10
0.75/1.0 4.1 10
1.1/1.5 5.9 10
1.5/2.0 7.5 10
2.2/3.0 9.4 15
FRAME 3 : 3-Phase (IT/TN), 200V
Drive Power
Drive PowerDrive Power
Drive Power
(kW/hp)
(kW/hp)(kW/hp)
(kW/hp)
Input Current @ 10kA
Input Current @ 10kAInput Current @ 10kA
Input Current @ 10kA
(A)
(A)(A)
(A)
Supply Fuse Rating (A)
Supply Fuse Rating (A)Supply Fuse Rating (A)
Supply Fuse Rating (A)
10 x 38mm
10 x 38mm10 x 38mm
10 x 38mm
2.2/3.0 9.6 15
3.0/4 12.3 20
4.0/5 16.4 20
FRAME 3 : 3-Phase (IT/TN), 400V
Drive Power
Drive PowerDrive Power
Drive Power
(kW/hp)
(kW/hp)(kW/hp)
(kW/hp)
Input Current @ 10kA
Input Current @ 10kAInput Current @ 10kA
Input Current @ 10kA
(A)
(A)(A)
(A)
Supply Fuse Rating (A)
Supply Fuse Rating (A)Supply Fuse Rating (A)
Supply Fuse Rating (A)
10 x 38mm
10 x 38mm10 x 38mm
10 x 38mm
3.0/4 11.1 15
4.0/5 13.9 20
5.5/7.5 18.0 25
7.5/10 23.6 30
Field Grounding Terminals
The field grounding terminals are identified with the International Grounding Symbol
(IEC Publication 417, Symbol 5019).
Operating Ambient Temperature
Devices are considered acceptable for use in a maximum ambient temperature of 40°C (can be
derated up to 50°C).