Specifications
10
Remote Alarm Option 
The DC-UPS Remote Alarm Option provides relay contacts to remotely monitor the status 
of the  unit.  These  alarms  will  indicate  either an  AC Fail or a Battery  Test Fail  condition. 
Both  normally open and  normally closed contacts are provided to suite the user’s external 
monitoring circuitry. The alarm contacts have a 2 Amp rating. The NO and NC contacts will 
change state when an alarm condition occurs.  
The alarm contacts are accessible via an RJ45 connector on the side panel of the DC-UPS. 
The Alarm Contact connector pinouts are shown in Figure 2 
Pin #  Function  Comment 
1  Battery Test Fail NC  Battery OK 
2  Battery Test Fail Common   
3  Battery Test NO  Battery has failed 
4  No connection   
5  No connection   
6  AC Fail NC  AC Failure has occurred  
7  AC Fail Common   
8  AC FAIL NO  Operating Normally 
Alarm Contact pinouts 
Figure 2 
Power Management Package 
SEI’s Power Management Package (PMP) for the SEI-DC-UPS provides a variety of 
functions necessary to monitor and control output power to DC powered devices, as well 
as maximize the efficiency and reliability of the power systems and battery backup. 
Ethernet communication is accessed via a panel mounted standard RJ45 connector. Two 
Ethernet interfaces are provided to monitor and control the DC-UPS. A web page 
interface that can be viewed with any Internet browser is available for easy system status 
checks and fast system configuration tasks. An SNMP interface provides the ability to 
continuously monitor the DC-UPS status with a Network Management System (NMS) 
and to receive instantaneous notification of DC UPS status changes and alarms via 
SNMP traps. 