Specifications

13
Appendix
Output Module –A
The –A version output module contains two individually fused TYCO/AMP Mat-N-
Lok connectors.
Mating Connector: 1-480698-0
Mating Pin: 350873-3
Wire Gauge: 14-18 AWG
Fuse: PORT 1, PORT2
GMT-7.5A, Cooper Bussmann or Equivalent.
PORT3, PORT4, PORT 5, PORT6
GMT-15A, Cooper Bussmann or Equivalent
Note: The fuse is sized to provide full output power from each connection. If multiple
connections are used, the fuse can be re-sized to limit current at a lower value.
+48V RTN
+48V
FUSE 1
FUSE 2
OUTPUT MODULE –A
Layout and Polarity