Specifications
15
Output Module –P 
Each port contains two ¼ -20 terminal posts suitable for ring lug connection. The 
48VRTN connection of each port is fused. 
Fuses:     
Ports 1-2      3AG 6A, 0312006 Littlefuse or Equivalent. 
Ports 3-6      3AG 15A, 326015 Littlefuse or Equivalent. 
Note:    The  fuse  is  sized to  provide  maximum  output  power  from each  connection.    If 
multiple connections are used, the fuse can be re-sized to limit current at a lower value. 
PORT 1
PORT 2
+48V
48VRTN
+48V
48VRTN
OUTPUT MODULE P 
Layout and Polarity 