Technical data of input (at 25°C) HD D0340I
Control voltage range 4 ... 30 VDC
Control current 0,3 ... 2,5 mA
Release voltage 2 V
Load current range at T
ambient
>0°C 2…40 A
Load current range at T
ambient
<0°C 4 … 40 A
Load circuit frequency range 15 … 200 Hz
Input LED green
Voltage range of the external digital input 4 ... 30 VDC
Control current of the external digital input 0,3 ... 2,5mA
External digital release voltage 2V
Max. reverse voltage 30V
Input immunity: EN61000-4-4 1kV
Input immunity: EN61000-4-5 1kV
Example of wiring with
several modules
The diagnostic outputs of several
modules (max. 5) can be
connected in parallel to one input
of a controller.
In the event of a fault, the controller
detects a fault and the „Fault“ LED
makes it possible to identify the
fault type and fault location on the
modules.
Current monitoring module for
HD series solid state relays
Current monitoring HD D0340I