Brochure
ESG
8.318.31
8.318.31
8.31
Technical data of power supply (at 25°C) HD D0340I
Voltage range 8 ... 30 VDC
Control current <20 mA
Polarity reversal protection yes
Surge voltage protection Varistor
Technical data of diagnostic output (at 25°C) HD D0340I
Voltage range 8 … 30 VDC
Output current 0,1 A
Output resistance closed 0,2 Ω
Max. leakage current 0,3 A
Switch-on time on power failure or no-load tc1 40 ms
Switch-off time on power failure or no-load to1 10 ms
Switch-on time on relay short circuit tc2 10 ms
Switch-off time on relay short circuit to2 40 ms
Switch-on time on temporary no-load or overload tc3 100 ms
Switch-off time on temporary no-load or overload to3 100 ms
Max. start-up time for load current ts 200 ms
Generalities HD D0340I
Article number 42310270
Order data see chapter 1)
Current monitoring module for
solid state relays type HD
Current monitoring module HD D0340I
Compliant with EN60947-4-3 (IEC947-4-3) and EN60950/VDE0805
(Reinforced Insulation) -UL-cUL pending
Technical data in general (at 25°C) HD D0340I
Switch-on time @ 50Hz (t
on
)15 ms
Switch-off time @ 50Hz (t
off
)15 ms
Diameter of cable entry for current converter 9 mm
Index of protection CEI520 IP20
Vibration (10 … 55Hz acc. to IEC 60068-2-6) 2 gn
Schock (1/2 sinusoidal/11 ms acc. to IEC 60068-2-27) 15 gn
Operating temperature range -40 … +80°C
Storage temperature range -40 … +125°C
Relative humidity 40 … 85%
Weight 75 g
Compliance with EN60947-4-3 (IEC947-4-3)
Compliance with EN60950 / UL/cUL
Housing material PA 6 UL94V0