AC/DC HALL EFFECT CURRENT TRANSDUCERS WITH 0-10 V OUTPUT
T201DCH T201DCH100 T201DCH300
AC/DC contactless TRMS direct and alternate
current transducer
AC/DC contactless TRMS direct and alternate
current (± 100 A) transducer, Hall Effect
AC/DC contactless TRMS direct and alternate
current (± 300 A) transducer, Hall Effect
HALL
EFFECT
HALL
EFFECT
HALL
EFFECT
GENERAL DATA
Power supply
10..28 Vdc 12..28 Vdc 12..28 Vdc
Power consumption
< 25 mA < 25 mA < 25 mA
Isolation / protection
3 kVdc (on bare conductors) 3 kVdc (on bare conductors) 3 kVdc (on bare conductors)
Installation category
300 V CAT III (bare conductor);
600 V CAT III (bare conductor)
300 V CAT III (bare conductor);
600 V CAT III (bare conductor)
300 V CAT III (bare conductor);
600 V CAT III (bare conductor)
Measurement polarity
Positive (incoming current on label side) Positive (incoming current on label side) Positive (incoming current on label side)
Protection degree
IP20 IP20 IP20
Response time
Fast filter: 800 ms - Slow filter: 2 s Fast filter: 800 ms - Slow filetr: 2 s Fast filter: 800 ms - Slow filetr: 2 s
Accuracy class
AC: 0,5% f.s
DC: 1% f.s.
AC: 0,5% f.s.
DC: 1% f.s.
AC: 0,5% f.s,
DC: 1% f.s.
Thermal drift
< 200 ppm/K < 200 ppm/K < 200 ppm/K
Settings
DIP switch
DIP switch
DIP switch
Operating temperature
-10..+65°C
-20..+70°C
-20..+70°C
Storage temperature
-40..+85°C
-40..+85°C
-40..+85°C
Humidity
10..90%RH non condensing
10..90%RH non condensing
10..90%RH non condensing
Connections
Removable terminals
Removable terminals
Removable terminals
Max diameter conductor
20,5 mm
20,5 mm
20,5 mm
Dimension
54 x 41 x 30 mm
68 x 97 x 26 mm
68 x 97 x 26 mm
Mounting
35 mm DIN rail with adapter
35 mm DIN rail with adapter
35 mm DIN rail with 2 adapters / screws
Weight
50 g
100 g
100 g
INPUT DATA
Channels
1 1 1
Range
0..25, 0..50 Aac/dc TRMS 0-50 A, 0-100 Aac/dc TRMS;
±50 A, ±100 A Bipolar
0-150 A, 0-300 Aac/dc TRMS;
±150 A, ±300 A Bipolar
Measurement type
TRMS AC/DC TRMS or DC Bipolar AC/DC TRMS or DC Bipolar
Bipolar measurement
No Yes Yes
Hysteresis
0,1 % f.s. 0,1 % f.s. 0,1 % f.s.
Max instantaneous overcurrent
2000 A (impulsive) 2000 A (impulsive) 2000 A (impulsive)
Bandwidth / frequency
1 kHz 1 kHz 1 kHz
Crest factor
1,2 2 2
OUTPUT DATA
Channels
1 1 1
Range
0..10 V 0..10 V 0..10 V
Resolution
12 bit 12 bit 12 bit
Max load
> 2 kOhm > 2 kOhm > 2 kOhm
STANDARD
Approvals
CE, UL-UR CE, UL-UR CE, UL-UR
Norms
EN61000-6-4
EN61000-6-2
EN61010-1
EN61000-6-4
EN61000-6-2
EN61010-1
EN61000-6-4
EN61000-6-2
EN61010-1
ORDER CODES
Model
T201DCH
AC/DC contactless TRMS direct
and alternate current transducer
T201DCH100
AC/DC contactless TRMS direct
and alternate current (± 100 A) transducer, Hall Effect
T201DCH100
AC/DC contactless TRMS direct
and alternate current (± 300 A) transducer, Hall Effect
SPARE PARTS
A-DIN-T201
DIN rail Plastic clip for T201