User Manual

MI004500-E ENGLISH - 4/4
Disposal of electrical & electronic equipment (applicable throughout the EU and other countries
wit separate collection programs). This symbol, found on your product or on
its packaging, indicates that this product should not be treated as household waste when you
wish to dispose of it.Instead,it should be handed over to an applicable collection
point for the recycling of electrical and electronic equipment. By ensuring this product is
disposed of correctly, you will help prevent potential negative consequences to the
environment and human health, which could otherwise be caused by inappropriate disposal of
it. The recycling of materials will help to conserve natural resources. For more
detailed information about the recycling of this product, please contact your local city office,
waste disposal service or the retail store where you purchased this product.
Multi-turn primary winding to improve sensibility
You can increase the sensibility of the device simply passing several times in the hole
with the measuring current, realizing turns with multiplicative effect:
For example, passing 5 times in the hole, as to see 4 turns, choosing a 50 A range,
you get an equivalent sensibility of 10 A full-scale. When you make this, let dispose the
turns with symmetry in order to preserve accuracy: use diametric contraposition with 2
turns, cross disposition with 4 turns, with 6 turns as like as 4 + 2, and so on.
Mounting
The device can be located in any position and place, in accordance with the operating
conditions above stated. Use the included holder bracket when fixing to a DIN rail.
High-strength magnetic fields may change the measured output value:WARNING:
Let avoid closeness to permanent magnets, electromagnets or iron bulks that cause
such a modification of the surrounding magnetic field; try a different arrangement or
orientation if zero error was greater than expected.
Supplied accessory for DIN rail mounting.
Settings:
(see manual)
AC/DC TRMS current transducer
Made in ITALY
T201DC H100-LP
T201DC H300-LP
Filter
Range
On
4
3
2
1
S1
Mode
+
MI004500-E
ENGLISH - 3/4
Input (A)
Input (A)
-100
-300
+100
+300
4 +50
+150
-50
-150
20
12
20
4
±100
±300
±50
±150
12
In the table the symbol corresponds to the switch in the ON position. The instrument is
factory delivered with range 100A (T201DCH100-LP) or 300A (T201DCH300-LP),
800ms filter and RMS mode.
DIP-switches
Range Filter (10% – 90%) Mode Not Used
1 DCH100 DCH300 2 DCH100 - 300 3 DCH100 - 300 4 DCH100 - 300
0 – 100A 0 – 300A Filter = 800ms TRMS /
Must be OFF
0 – 50A 0 – 150A
Filter = 2000ms
DC Bipolar
OPERATING CONDITION
Protection degree IP20
Operating temperature -20 – +70 °C
Storage Temperature -40 – +85 °C
Humidity 10 – 90 % non-condensing
Altitude Up to 2000 m a.s.l.
CASE
Weight 47 g.
Overall dimensions 96,5 x 68 x 26 mm (without terminals)
Box material PA6, black color
STANDARDS
EN61326 (EMC requirements)
EN61010-1 (safety)
MI004500-E
ENGLISH - 2/4
Technical features
INPUT
Measure type AC / DC TRMS or Bipolar DC
Range T201DCH100-LP
Range T201DCH300-LP
0 – 50A or 0 – 100A TRMS; -50 – +50A or -100 – +100A Bipolar
0 – 300A or 0 150A TRMS; -150 – +150A or -300 – +300A Bipolar
( )selectable by dip-switch.
Peak factor 1.3
Bandwidth 1 kHz
Insulation
When a sheathed wire is used, the insulation voltage is set by
sheath properties. On a bare wire, it’s stated to 3 kV
Over-current 2000 A impulsive, 500 A permanent
OUTPUT AND POWER SUPPLY
Type
4 – 20 mA, max. load R =600 .
LOAD
Ω
Screw terminals: and
Terminals Screw terminal pitch 5.08mm for max 2.5 mm
2
cables
Hole diameter 20.8 mm
Power supply 9 – 28 V (between and )
Protections
- Polarity reversal
- Over-Voltage
Fail indication < 3.8 mA
Max. indication < 22 mA
PRECISION
Range Precision
Precision
Over the 2%
of End of Scale
100 A or 300 A
50 A or 150 A
0.5% of end scale.
1% of end scale.
1% of end scale.
2% of end scale.
Under the 2%
of End of Scale
100 A or 300 A
50 A or 150 A
1% of end scale.
2% of end scale.
2% of end scale.
4% of end scale.
Resolution Output: 10 bit (1000 points) Input: 12 bit (4000 points).
Temperature coefficient < 200 ppm/°C
Error due to EMI < 1%
Response time - Fast filter: 500 ms.
- Slow filter: 1000 ms.
Measure hysteresis 0.3% of the end scale (typical)
OVERVOLTAGE CATEGORY
Bare conductor CAT. III 300V
Insulated conductor CAT. III 600V
MI004500-E
ENGLISH - 1/4
This document is property of SENECA rl. Duplication and reproduction are forbidden, if not authorized. ContentsS
of the present documentation refers to products and technologies described in it. All technical data contained in
the document may be modified without prior notice.Content of this documentation is subject to periodical revision.
SENECA s.r.l.
Via Austria, 26 – 35127 – PADOVA – ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
Manuals and configuration software are available at website:
www.seneca.it/products/t201dch100-lp and www.seneca.it/products/t201dch300-lp
Technical support: support@seneca.it Product Informations: sales@seneca.it
General Specifications
Direct and alternating current tran ducer s
galvanically insulated from the measuring circuit
Measurement principle: Hall Effect
Possibility to measure the direct and alternating
component of TRMS current
No shunt, no wasted power of primary current
Circuit and no dissipation.
Unipolar or bipolar measurement.
High measurement accuracy: .
0.5% 1%
Suitable for Seneca modules with power supply
sensors at 12V and input 4-20 mA.
Two DIP-Switches selectable ranges.
Damping filter availability to improve stable
reading.
Suitable for batteries, battery chargers, solar
panels, power units and generic dc loads.
Compact overall dimensions: .96,5 x 68 x 26 mm