User Manual

MI004431-E
ENGLISH - 4/4
S
seneca
Mounting
The device can be located in any position and place, in accordance with the operating
conditions above stated. Use the included holder bracket when fixing it to a DIN rail.
: High-strength magnetic fields may change the output value: let avoid closenessWARNING
to permanent magnets, electromagnets or iron bulks that cause such a modification
of the surrounding magnetic field; try a different arrangement or orientation if zero error was
greater than expected.
Multi-turn primary winding to improve sensibility
You can increase the sensibility of the device simply passing several times in the hole with
the measuring current, realizing turns with multiplicative effect: for example, passing 5 times
in the hole, as to see 4 turns, choosing a 50 A range, you get an equivalent sensibility of 10 A
full-scale. When you make this, let dispose the turns with symmetry in order to preserve
accuracy: use diametric contraposition with 2 turns, cross disposition with 4 turns, 60° with 6
turns, and so on.
Disposal of electrical & electronic equipment (applicable throughout the EU and other countries wit separate collection programs). This symbol, found on your product or on its packaging,
indicates that this product should not be treated as household waste when you wish to dispose of it.Instead,it should be handed over to an applicable collection point for the recycling of
electrical and electronic equipment. By ensuring this product is disposed of correctly, you will help prevent potential negative consequences to the environment and human health, which
could otherwise be caused by inappropriate disposal of it. The recycling of materials will help to conserve natural resources. For more detailed information about the recycling of this product,
please contact your local city office, waste disposal service or the retail store where you purchased this product.
MI004431-E
ENGLISH - 3/4
S
seneca
20
0
±50
±25
4
-50
+50
0
20
12
+25-25
12
4
TRMS Output (mA)
Input (A)
Input (A)
Bipolar
output (mA)
In the table the symbol corresponds to the switch in the ON position;Ç
The instrument is factory delivered with range 50A, 800ms filter and RMS mode.
DIP-switches
Range
Filter (10% 90%)
Mode
Not used
DIP Switch 1
DIP Switch 2
DIP Switch 3
DIP Switch 4
0 50A
Filter = 500ms
È
Must be OFF
Ç
0 25A
Ç
Filter =1000ms
Ç
OVERVOLTAGE CATEGORY
Bare conductor
CAT. III 300V
Insulated conductor
CAT. III 600V
OPERATING CONDITION
Protection degree
IP20.
Operating temperature
-20 +70 °C.
Storage Temperature
-40 +85 °C.
Humidity
10 90 % non-condensing.
Altitude
Up to 2000 m a.s.l.
CASE
Weight
47 g.
Overall dimensions
41 x 44 x 26 mm (without terminals).
Box material
PA6, black color
MI004431-E
ENGLISH - 2/4
S
seneca
Technical features
INPUT
Measure type
AC / DC TRMS or Bipolar DC
Range
0-50 Arms, 0-25 Arms, -50 +50 A Bipolar or -25 +25 A Bipolar,
selectable by dip-switch.
Peak factor
1.3
Bandwidth
1 kHz
Insulation
When a sheathed wire is used, the insulation voltage is set by
sheath properties. On a bare wire, it’s stated 3 kV A
Over-current
300 A permanent
OUTPUT AND POWER SUPPLY
Type
4 20 mA, max. load R =600 . Screw terminals: and .
LOAD
Ω p m
Terminals
Screw terminal pitch 5.08mm for max 2.5 mm
2
cables.
Hole diameter
12.3 mm
Power supply
9 28V (between and ).C p p
Protections
- Polarity reversal
- Over-Voltage.
Fail indication
< 3.8 mA
Max. indication
< 22 mA
ACCURACY
Range
Precision A
Precision C
Over the 2%
of End of Scale
50 A
25 A
0.5% of end scale..
1% of end scale.
1% of end scale.
2% of end scale.
Under the 2%
of End of Scale
50 A
25 A
1% of end scale.
2% of end scale.
2% of end scale.
4% of end scale.
Resolution
Output: 10 bit (1000 points) Input: 12 bit (4000 points).
Temperature coefficient
< 200 ppm/°C.
Error due to EMI
< 1%
Response time
- Fast filter: 500 ms.
- Slow filter: 1000 ms.
Measure hysteresis
0.3% of the end scale (typical)
NORMATIVE
EN61326 (EMC requirements).
EN61010-1 (safety).
ENGLISH - 1/4
MI004431-E
S
seneca
General Specifications
Direct and alternating current tran ducers
galvanically insulated from the measuring circuit.
Measurement principle: Hall Effect
Possibility to measure the direct and alternating
component of TRMS current.
No shunt, no wasted power of primary current
circuit and no dissipation.
Unipolar or bipolar measure.
High measurement accuracy: 0.5 %.
Suitable for Seneca modules with power supply
sensors at 12V and input 4-20 mA.C
Two DIP-Switches selectable ranges.
Damping filter availability to improve stable
reading.
Suitable for batteries , battery chargers, solar
panels, power units and generic dc loads.
Compact overall dimensions: 41 x 44 x 26 mm.
T Series - Field converters
T201DCH50-LP
Contact-less direct and alternating
TRMS current transducer
EN
This document is property of SENECA rl. Duplication and reproduction are forbidden, if not authorized.S
Contents of the present documentation refers to products and technologies described in it. All technical
data contained in the document may be modified without prior notice.Content of this documentation is
subject to periodical revision.
SENECA s.r.l.
Via Austria, 26 35127 PADOVA ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
Manuals and configuration software are available at website: www.seneca.it/products/t201dch50-lp
Technical support: support@seneca.it Product Informations: sales@seneca.it

Summary of content (1 pages)