Product Overview
www.senjusprinkler.com Document No.U087474 • 01-29-2021 Page 1 of 8
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder
type. They are decorative and fast responding. The Cover Plate Assembly hides the Deector, Heat Responsive Element
etc., which is concealed above the ceiling. The cover plate has a at prole, and its diameter is extremely small (2-5/8
inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy
installation of the cover plate. Therefore, the Model RC-RES should be your rst choice when aesthetics is the major
consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential
occupancies and is perfect for use in homes, hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per
NFPA 13.
The Model RC-RES has a 5.8 (83.6 LPM/bar
1/2
) K-factor that meets the required residential ow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation exibility, the
Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for
precise cutting of the pipe that drops to the sprinkler and allows for a perfect t with a range of pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape
or evacuate in case of a re. However, residential re sprinkler systems are not a substitute for re safety awareness or re
safety construction required by building codes.
“Lead Free” is dened in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA’s Water Utility Council,
and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of
pipes, plumbing ttings and xtures.
GENERAL DESCRIPTION
Residential Lead Free
Flat Concealed Sprinkler, Pendent
Model RC-RES
K-Factor: 5.8
•
SIN: SS8561
C US
NSF/ANSI/CAN 61 & 372