Product Overview

www.senjusprinkler.com Document No.U087474 • 01-29-2021 Page 1 of 8
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder
type. They are decorative and fast responding. The Cover Plate Assembly hides the Deector, Heat Responsive Element
etc., which is concealed above the ceiling. The cover plate has a at prole, and its diameter is extremely small (2-5/8
inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy
installation of the cover plate. Therefore, the Model RC-RES should be your rst choice when aesthetics is the major
consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential
occupancies and is perfect for use in homes, hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per
NFPA 13.
The Model RC-RES has a 5.8 (83.6 LPM/bar
1/2
) K-factor that meets the required residential ow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation exibility, the
Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for
precise cutting of the pipe that drops to the sprinkler and allows for a perfect t with a range of pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape
or evacuate in case of a re. However, residential re sprinkler systems are not a substitute for re safety awareness or re
safety construction required by building codes.
“Lead Free” is dened in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWAs Water Utility Council,
and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of
pipes, plumbing ttings and xtures.
GENERAL DESCRIPTION
Residential Lead Free
Flat Concealed Sprinkler, Pendent
Model RC-RES
K-Factor: 5.8
SIN: SS8561
C US
NSF/ANSI/CAN 61 & 372

Summary of content (8 pages)