Datasheet
Panel Mount
INPUT SPECIFICATIONS
(1)
Description 8413xxx0
Control Voltage Range 3-32 VDC (4)
Maximum Reverse Voltage -32 VDC
Minimum Turn-On Voltage 3 VDC (4)
Must Turn-Off Voltage 1 VDC
Minimum Input Current (for on-state) [mA] 10
Maximum Input Current [mA] 15
Nominal Input Impedance [Ohms]
Maximum Turn-On Time [msec] 1/2 Cycle (6)
Maximum Turn-Off Time [msec] 1/2 Cycle
8413xxx1
90-280 VAC (5)
-
90 VAC
10 VAC
6
10
20
30
8413xxx2
18-36 VAC
-
18 VAC
4 VAC
13
15
Current Regulated
20
30
GENERAL SPECIFICATIONS
(1)
ParametersDescription
Dielectric Strength, Input/Output/Base (50/60Hz) 4000 Vrms
Minimum Insulation Resistance (@ 500 VDC)
10
9
Ohms
Maximum Capacitance, Input/Output 8 pF
Ambient Operating Temperature Range (7) -40 to 80 °C
Ambient Storage Temperature Range -40 to 125 °C
Weight (typical) 2.53 oz (72 g)
Housing Material UL94 V-0
Baseplate Material Aluminum
Input Terminal Screw Torque Range (in-lb/Nm) 13-15 /1.5-1.7
Load Terminal Screw Torque Range (in-lb/Nm) 18-20 / 2-2.2
SSR Mounting Screw Torque Range (in-lb/Nm) 18-20 / 2-2.2
LED Input Status Indicator Green
MTBF (Mean Time Between Failures) at 40°C ambient temperature (8)
11,641,553 hours (1,328 years)
MTBF (Mean Time Between Failures) at 60°C ambient temperature (8)
7,210,376 hours (823 years)
Humidity per IEC60068-2-78 93% non-condensing
GENERAL NOTES
For additional information or specific questions, contact Crydom Technical Support.
(1)
All parameters at 25°C unless otherwise specified.
(2) Output will self trigger between 450-600 Vpk / 900-1200 Vpk for 280 VAC/660 VAC models not suitable for capacitive loads.
(3) Heat sinking required, see derating curves.
(4) 4-32 VDC for 48-660 VAC models.
(5) For ambient temperatures above 40°C the maximum control voltage must not exceed 250 VAC.
(6) Turn-on time for Instantaneous turn-on versions is 0.1 msec.
(7) AC models operating range is -20 to 80°C.
(8) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(9) Load can be wired to either SSR output terminal 1 or 2.
(10) For single surge pulse Tc=25°C; Tj=125°C. For AC Output SSRs, AC Rms value of surge current equals the peak value divided by √2 (1.414).