PRODUCT SELECTION
30A20A10AControl Voltage
4-32 VDC Control CKRD2410 CKRD2420 CKRD2430
110-280 VAC Control CKRA2410 CKRA2420 CKRA2430
90-140 VAC Control CKRB2410 CKRB2420 CKRB2430
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
30A20A10ADescription
Operating Voltage (47-63Hz) [Vrms] 24-280 24-280 24-280
Transient Overvoltage [Vpk] 600 600 600
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2) 500 500 500
Maximum Load Current [Arms] 10 20 30
Minimum Load Current [Arms] 0.15 0.15 0.15
Maximum Surge Current (16.6ms) [Apk] 120 250 1200
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6
Maximum I² t for Fusing (8.3 msec) [A² sec] 60 260 6000
Minimum Power Factor (with Maximum Load) 0.5 0.5 0.5
CKR24 Series
• Rating from 10A to 30A @ 280VAC
• Slim 22.5mm (width) package
• SCR output for heavy industrial loads
• LED input status indicator
• AC or DC control
• Zero Voltage (resistive loads) or Instantaneous (inductive loads) turn-on output
18-36 VAC Control CKRA2410E CKRA2420E CKRA2430E
Required for valid part number
For options only and not required for valid part number
Series
Overvoltage Protection
Blank: Not Included
P: Included
Switching Type
Blank: Zero Voltage Turn-On
-10: Instantaneous Turn-On
Operating
Voltage
24: 24-280 VAC
CKR 10 -10E P24D
Rated Load Current
10: 10 Amps
20: 20 Amps
30: 30 Amps
Control Voltage
D: 4-32 VDC
B: 90-140 VAC
A: 110-280 VAC
AxxxxE: 18-36 VAC