Datasheet

Datasheet
I/O Modules
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
DR OUTPUT MODULES
DIN Rail Mountable Single Point Output Modules (35mm DIN)
Plug into mounting boards for 0.6" modules
Zero Voltage Turn-On for AC Modules
4kV Optical isolation with LED Indicator
UL Recognized, CSA Certified, CE Compliant
Industry standard Color Coding Black (AC Output) Red (DC Output)
Barrier Strips Accept 14 to 28 AWG Wire.
SPECIFICATIONS
Input
42CDO-RD5CDO-RDCAO-RDrebmuN traP
Nominal Voltage [VDC] 5-24 5.0 24.0
Minimum Voltage [VDC] 3.7 3.5 18.0
Maximum Voltage [VDC] 32 8.0 32.0
Drop-out Voltage [VDC] 1.0 1.0 1.0
Maximum Current [mA] (2) 18 18 13
Resistance [Ohms] (3) NA 250 2000
Output
Nominal Line Voltage 240 VAC 5-48 VDC 5-48 VDC
Minimum Line Voltage 12 VAC 3 VDC 3 VDC
Maximum Line Voltage 280 VAC 60 VDC 60 VDC
Max Off-State Voltage (4) 600 Vpeak 60 VDC 60 VDC
Max Off-State Leakage (5) 0.1mArms 10 uA 10 uA
Static Off-State dv/dt (6) 200 V/usec N/A N/A
Maximum Rated On-State Current (7) 5.0 Arms 3.0 A 3.0 A
Minimum On-State Current 50 mArms 10 mA 10 mA
Max Surge Current (8) 250 Apeak 5.0 A 5.0 A
On-State Voltage Drop or Resistance (9) 1.6 V 1.6 V 1.6 V
Horse Power Rating (10) 1/2 H.P. N/A N/A
Fuse (11) 5 5 5
Maximum Turn-On Time [msec] (12) 8.33 0.1 0.1
Maximum Turn-Off Time [msec] (12) 8.33 0.75 0.75
Input/Output Isolation Voltage (13) 4000 Vrms 4000 Vrms 4000 Vrms
Input/Output Capacitance 8 pF 8 pF 8 pF
Operating Temperature Range -30 to 80°C -30 to 80°C -30 to 80°C
Storage Temperature Range -40 to 80°C -40 to 80°C -40 to 80°C
Line Frequency Range 47 to 63 Hz DC DC
Weight 1.1 oz. (31.2g) 1.1 oz. (31.2g) 1.1 oz. (31.2g)
General Notes:
(1)
Specifications apply to an ambient temperature of -30 to 80 °C unless otherwise noted.
(2)
At nominal input voltage, without external LED status indicator.
(3)
+/-10% at 25°C.
(4)
Maximum 1 minute duration for OAC modules when applied as a DC voltage rather than a peek AC voltage.
(5)
At maximum line voltage, 25°C for OAC modules, and 80°C for ODC modules.
(6)
Minimum DV/DT per EIA/NARM RS433, method RS397, DV/DT ratings do not apply to DC output models
(7)
At 40°C, derate OAC modules 58 mA/°C to 80°C, derate ODC. ODCxMC and ODCxML modules 50 mA/°C
to 80°C. CSA rating of OAC modules is 3.0 Arms at 40°C.
(8)
At 25°C for 1 second maximum duration: 1 AC cycle for AC modules, 1 second for DC modules.
(9)
At maximum rated on-state current and 25°C.
(10)
1/3 H.P. at 240 VAC, 1/8 H.P. at 120 VAC.
(11)
Fuse is BUSS # PCE5.
(12)
At maximum line voltage, maximum rated output current, nominal input voltage and 25°C. Switching speed
of OAC
modules is based upon 60 Hz line frequency.
(13)
At 25°C for 1 second maximum duration.
(1)

Summary of content (4 pages)