Datasheet

GNR 90mm Series
• Current rating: 25 amps
• Output voltage rating: 48-600 VAC
• Direct Bond Copper (DBC) Substrate
• LED input status indicator
• UL 508 Endurance Rating for Enhaced Reliability
• UL/CSA/TUV Approved, CE Compliant
• Built-in overvoltage protection
• DIN Rail or Panel Mount
• Zero voltage or Instantaneous turn-on output
PRODUCT SELECTION
Control Voltage Zero-Crossing Random Turn-on
4-32 VDC GNR25DCZ GNR25DCR
90-140 VAC GNR25BCZ
180-280 VAC GNR25ACZ
OUTPUT SPECIFICATIONS
(1)
Description
Operating Voltage (47-440Hz) [Vrms]
Transient Overvoltage [Vpk, t=1 min.]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Maximum Load Current [Arms]
Minimum Load Current [Arms]
Static Off-State dv/dt ( V/µsec, Ta=25°C)
(2)
1 Second Surge Current (Apk Ta=25°C) 50/60 Hz
Forward Voltage Drop (Vpk @ max, Ta=25°C)
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I² t for Fusing (50/60Hz, 1/2 cycle ) [A² sec]
HP Ratings at 240V / FLA [Arms]
HP Ratings at 380V / FLA [Arms]
HP Ratings at 480V / FLA [Arms]
Min/Max stranded wire
Min/Max solid wire
GNR25
48-600
1100
25
0.1
0.25
500
1.30
130
286/300
410/374
1/4.2
2/4.3
3/4.8
16/8 AWG
16/10 AWG
Datasheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
INPUT SPECIFICATIONS
(1)
Description
Control Voltage Range (3)
CTRB6025
90-140 Vrms
Minimum Turn-On Voltage
90 Vrms
Must Turn-Off Voltage
10 Vrms
Minimum Input Current (for on-state)
Maximum Input Current
Input Resistance
15 mArms
Maximum Turn-On Time [msec]
(4)
19 mArms
Maximum Turn-Off Time [msec]
20
Min/Max stranded/solid wire
30
24/16 AWG
CTRD6025
4.0-32 VDC
4.0 VDC
1.0 VDC
22 mA
28 mA
Current Regulated Current Regulated Current Regulated
1/2 Cycle
1/2 Cycle
24/16 AWG
CTRC6025
180-280 Vrms
180 Vrms
10 Vrms
19 mA
24 mA
20
30
24/16 AWG