Datasheet

GNR 22.5mm Series
Current ratings of 10, 20 and 30 amps
Output voltage ratings: 24-280 and 48-600 VAC
Direct Bond Copper (DBC) Substrate
LED input status indicator
UL 508 Endurance Rating for Enhanced Reliability
UL/CSA/TUV Approved, CE Compliant
Built-in overvoltage protection
DIN Rail or Panel Mount
Zero voltage or Instantaneous turn-on output
PRODUCT SELECTION
Control Voltage 10A 30A
4-32 VDC GNR10DHZ
90-140 VAC GNR10BHZ
180-280 VAC GNR10AHZ
GNR30DHZ
GNR30BHZ
GNR30AHZ
20A
GNR20DHZ
GNR20BHZ
GNR20AHZ
OUTPUT SPECIFICATIONS
(1)
Description
Operating Voltage (47-440Hz) [Vrms]
Transient Overvoltage [Vpk, t=1 min.]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Maximum Load Current [Arms]
Minimum Load Current [Arms]
Static Off-State dv/dt ( V/µsec, Ta=25°C)
(2)
1 Second Surge Current (Apk Ta=25°C) 50/60 Hz
Forward Voltage Drop (Vpk @ max, Ta=25°C)
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
Maximum I² t for Fusing (50/60Hz, 1/2 cycle ) [A² sec]
HP Ratings at 120V / FLC [Arms]
HP Ratings at 240V / FLC [Arms]
Min/Max stranded wire
Min/Max solid wire
GNR10
24-280
600
0.1
500
10
100
65
190/200
1.5
182/166
-
-
16/8 AWG
16/10 AWG
GNR30
48-600
1100
0.1
500
30
100
150
716/750
1.35
2562/2334
3/4 / 13.8
2/12
16/8 AWG
16/10 AWG
GNR20
48-600
1100
0.1
500
20
100
85
286/300
1.35
410/374
1.2/9.8
1/8
16/8 AWG
16/10 AWG
Datasheet
DIN Rail Mount
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
AVAILABLE OPTIONS
Required for valid part number
For options only and not required for valid part number
Series
Operating Voltage
A: 180-260 VAC
B: 90-140 VAC
D: 4-32 VDC
Rated Load Current
10: 10 Amps
20: 20 Amps
30: 30 Amps
GNR A H Z10
Terminal Layout
C: Contactor configuration
H: Relay configuration
Switching Type
R: Instantaneous Turn-on
(for DC control only)
Z: Zero voltage Turn-on

Summary of content (6 pages)