DC to AC POWER INVERTERS Pure Sine Wave Output OWNER’S MANUAL MODELS: 12/800N 12/1200N 12/1500N MODELS: 12/1800N 12/2400N 12/3000N 12/3600N
TABLE OF CONTENTS SAFETY INSTRUCTIONS ............................................................................................................. .............................................................................................................2 Inverter Safety Instructions ....................................................................................................... .......................................................................................................
SAFETY INSTRUCTIONS IMPORTANT: Read this manual before installation, it contains important safety, installation, and operating instructions. Save this manual and keep it in a safe place. NOTE: This product is Listed to applicable UL Standards and requirements by Underwriters Laboratories Inc., File E100666. Sensata Technologies is an ISO 9001:2008 Registered Company.
Battery Safety Information: WARNING: Working in the vicinity of lead-acid batteries is dangerous. There is a risk of acid exposure. WARNING: Batteries generate explosive gases during operation. WARNING: There is risk of high current discharge from shorting a battery that can cause fire and explosion. Use insulated tools during installation. WARNING: Remove all rings, watches, jewelry or other conductive items before working near the batteries.
NOMENCLATURE MOUNTING THE INVERTER Installation Tools The following tools are required for inverter installation: Crimper, Cable Ties, Cutter, Drill, #2 Phillips Screw Driver, Tape Measure, Wire Cutters, and Wire Strippers. Inverter Mounting Recommendations 3 9 3 CASE “I” 1.5 2.5 8.2 4 5 2.5 1.5 15 Inverter Models 12/800N & 12/1200N, & 12/1500N 16 CASE “L” 2 5.5 4.5 2.5 15 17 CASE “O” 16 15.
DC WIRE GAUGE, FUSING & BATTERIES Inverter Cable An “Inverter Cable” kit (positive cable, negative cable, and proper fuse) is required to connect the inverter to a battery pack. An 8-guage cable is also required to connect the inverter’s bonding lug to ground. The inverter cable length and the size of the inverter will determine the cable gauge and the size fuse to use. The maximum inverter cable recommended is 20-ft; it must be fused within 18-in from the positive (+) terminal of the battery.
HARDWIRE OUTPUT The hardwire A.C output is not ground fault interrupt, (GFCI) protected unless the inverter has option “A”. GFCI outlets should be installed at all appropriate locations per NEC 551. The GFCI outlet should be Leviton Type 7899 or N7899, 20Amp., 125VAC.
Typical Wiring Diagram for 12/1800N, 12/2400N, 12/3000N, 12/3600N 7
Typical DC Cable Connections for 12/800N, 12/1200N & 12/1500N 8
Typical DC Cable Conn’s for 12/1800N, 12/2400N, 12/3000N, &12/3600N 9
INVERTER TROUBLESHOOTING GUIDE Status Panel 12/1800N, 12/2400N, 12/3000N, & 12/3600N Status Panel 12/800N & 12/1200N Plug a 100-watt light bulb into the inverter’s AC outlet. Switch on the remote On/Off switch (if available). Switch the inverter’s AC outlet On/Off for 5 seconds: then, switch it back ON. If the work light lights, the inverter works. Symptom Possible Cause(s) Solution(s) No inverter indicators are on and work light not ON. 1. No DC power to inverter. 2.
Troubleshooting Steps Step 1. INVERTER POWER indicator LED is not ON. A. Locate the small violet wire in the front of the inverter. Disconnect the violet wire from the external remote switch circuit. Connect the violet wire to the large positive DC input lug on the front of the inverter. 1. If the inverter powers ON, the fault exists in the remote On/Off circuit. Possible problems include: • A failed remote circuit fuse. • A defective switch.
SPECIFICATIONS GENERAL SPECIFICATIONS 12/800N 12/1200N 12/1500N 12/1800N 12/2400N 12/3000N 12/3600N Output Power (Watts Continous) 800 1200 1500 1800 2400 3000 3600 Output Current (Amps AC) Up to 7 Up to 10 Up to 12.5 Up to 15 Up to 20 Up to 25 Up to 30 Peak Output (Amps DC) 12 21 24 44 91 91 136 Input Current (Amps DC) Up to 80 Up to 120 Up to 150 Up to 180 Up to 240 Up to 300 Up to 360 Input Voltage (Volts DC) 10.
LIMITED WARRANTY TERMS & CONDITIONS SHIPPING TERMS: F.O.B. St. Paul Minnesota. Freight prepaid and billed, subject to prior credit approval. MINIMUM ORDER: $50.00 Net Price LOSS OR DAMAGE: Loss or damage in transit is the responsibility of the carrier; any claim should be filed with the delivering transport company. Invoice, Bill of Lading and Delivery receipt with damage noted therein must accompany any claims for freight damage.
Notes: 14
Sensata Technologies Manufacturer of Dimensions Inverters 4467 White Bear Parkway St. Paul, MN 55110 Phone: 651-653-7000; 800-553-6418 Fax: 651-653-7600; 888-439-3565 inverterinfo@sensata.com www.dimensions.sensata.com Form No. 122187 (03/21/14) © Sensata Technologies 2014 Printed in U.S.A.