Product Manual
15
2) Inverter “Stby”
The inverter standby feature allows the inverter to automatically come on
anytime that it senses a loss of shore power and then go back to standby when
shore power is returned (after 22 seconds of line qualify time).
This feature is enabled by turning the inverter on by pressing the [ON/OFF]
key. If this is done while shore power is applied the “ON/STBY” LED will
come on Amber and the display will show:
Inv stby push Off
This message is stating that the inverter is in standby and that to exit this mode
you need to press the [ON/OFF] key.
NOTE - To exit Inverter standby mode, press the [ON/OFF] key.
If you turn off the inverter while shore power is applied the display will show:
Inv Off push stby
This message is stating that the inverter is off and that to put it back to standby
you need to push the [ON/OFF] (Stby) key.
3) Other inverter messages:
Inv LOW batt 9.8v
Low battery condition due to start surge or undersized battery cable gauge. If
this condition remains for => 5seconds the inverter will shutdown.
Inv OvL batt 11.8v
Overload condition due to excessive loads or short circuit. If this condition
remains for => 5seconds the inverter will shutdown.
4) Battery Test
The battery voltage can be tested at anytime by pressing the [BATT TEST]
key. The mode will stay active for 1 minute or until the [BATT TEST] or
[MENU] key is pressed.
12.6v
5) Battery Trough (low battery voltage point)
If while using the inverter, the inverter temporarily shuts down due to a low
DC input condition, you can check to see how low the DC input voltage
momentarily went to. To see this value, press the [BATT TEST] key. Then