Mount sensor directly to a ceiling tile or a metallic grid (two self-tapping
screws provided).
Sensors mounting holes also align with 3.5” octagon or single gang handy
box (screws not provided).
Sensor will detect motions crossing segments more effectively than motions
parallel to beams.
For optimal detection, position sensor such that segments are crossed upon
entrance and unable to view outside the space.
PDT models: For maximum Microphonics sensitivity avoid locating sensor
near HVAC air diffusers
PUSH BUTTON
*At 9ft Mtg.
A: When walking across beam,
detection will occur at approximately 28 feet.
(8.53 m)
B: When walking into beam, detection will
occur at approximately 24 feet. (7.32 m)
INSTALLATION
CM Family
STANDARD WIRING
RED - Power Input (12-24 VAC/VDC)
BLACK - Common
WHITE - Occupancy State (high VDC for occupied)
RELAY OPTION (R)
GRAY / BROWN - Connected during occupied state
VIOLET / BROWN - Connected during unoccupied state
Note: Relay is energized during unoccupied state
PHOTOCELL/DIMMING OPTIONS (D, P, ADC)
BLUE - Direct output to power pack for providing photocell control and/or
secondary dim time out. Output is high VDC with occupancy & low light.
Output also held high during secondary dim time out. For multi-level
control, use two power packs and connect White wire to primary load and
Blue to daylight load.
VIOLET w/ WHITE STRIPE - Connect to 0-10 VDC control wire (typically
Violet) from 0-10 VDC dimmable ballast
GRAY from Ballast - Connect to sensor Black wire
WIRING (DO NOT WIRE HOT)
[R] Relay Option
[D, P, ADC] Photocell / Dimming Options
POWER PACK
(PP20)
RED
WHT
BLK
VIO w/ WHT STRIPE (+)
(-)