Specification Sheet
3 of 3
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2014-2016 Acuity Brands Lighting, Inc. All rights reserved. 02/02/16
• Mount sensor directly to a ceiling tile or a metallic grid (two self-tapping
screws provided).
• Sensor’s mounting holes also align with 3.5” octagon or single gang handy
box (screws not provided).
• Sensor will detect motions crossing segments more effectively than motions
parallel to beams.
• For optimal detection, position sensor such that segments are crossed upon
entrance and unable to view outside the space.
• PDT models: For maximum Microphonics sensitivity avoid locating sensor
near HVAC air diffusers
PUSH BUTTON
*At 9ft Mtg.
A: When walking across beam,
detection will occur at approximately 28 feet.
(8.53 m)
B: When walking into beam, detection will
occur at approximately 24 feet. (7.32 m)
INSTALLATION
CM Family
STANDARD WIRING
RED - Power Input (12-24 VAC/VDC)
BLACK - Common
WHITE - Occupancy State (high VDC for occupied)
RELAY OPTION (R)
GRAY / BROWN - Connected during occupied state
VIOLET / BROWN - Connected during unoccupied state
Note: Relay is energized during unoccupied state
PHOTOCELL/DIMMING OPTIONS (D, P, ADC)
BLUE - Direct output to power pack for providing photocell control and/or
secondary dim time out. Output is high VDC with occupancy & low light.
Output also held high during secondary dim time out. For multi-level
control, use two power packs and connect White wire to primary load and
Blue to daylight load.
VIOLET w/ WHITE STRIPE - Connect to 0-10 VDC control wire (typically
Violet) from 0-10 VDC dimmable ballast
GRAY from Ballast - Connect to sensor Black wire
WIRING (DO NOT WIRE HOT)
[R] Relay Option
[D, P, ADC] Photocell / Dimming Options
POWER PACK
(PP20)
RED
WHT
BLK
VIO w/ WHT STRIPE (+)
(-)