Installation Guide

AMS-9080 CONTROLLER 8200-0914-01 REV. A
INSTALLATION GUIDE 9 of 22 *8200-0914-01*
Connecting the AC power
To connect the AC power to the AMS-9080 Controller, complete the following steps:
WARNING: In accordance with the USA National Electric Code and applicable US local codes, a
15 A or 20 A, two-pole, ganged disconnect device, which also provides short circuit and overload
protection and has a minimum 3-millimeter open circuit clearance, must be installed by a licensed
electrician at a location readily accessible to the equipment. If the only line providing power is the
primary/L1, you can use a single-pole breaker.
1. Locate the voltage shunt in a bag taped inside the controller.
WARNING: Risk of electric shock.
Ensure that you disconnect power from the controller before you move the shunts.
2. Select the proper voltage for the site using the shunt, 2109-0062-01. The default setting is 240 VAC.
3. The AMS-9080 Controller can receive AC power through a power cord, or through a hardwired connection.
Complete one of the following procedures:
Connecting the power cord
Hardwiring the AC connection
Figure 2. Voltage settings and shunts
A
120 VAC, J5 shunt IN
B
240 VAC, J5 shunt OUT
Connecting the power cord
In countries where code allows, you can connect the AC power using a power cord. To connect the AC power
using a power cord complete the following steps:
1. From Table 4, choose a power cord for the country of use.
Table 4. Power cord part numbers per country
Power cord
Part number
USA-IEC 320, 18/3, 125 V, 10 A, 7.5 ft
0351-0547-01
Schuko-IEC 320, 1 mm
2
, 250 V, 10 A, 2.5 m
0351-0547-02
UK-IEC 320, 1 mm
2
, 250 V, 10 A, 2.5 m
0351-0547-03
Japan-IEC 320, 2 mm
2
, 250 V, 15 A, 2.5 m
0351-0547-04
US-Filter, Line, 125 V, 6 A, Plug-in
0351-0547-05
Australia to IEC 320, 2.5 m, 250 V, 10 A
0351-0547-07