User's Manual

WGS Configuration Rev A
Page 12 FlexZone Wireless Gate Sensor
Auxiliary Input Configuration
Supervision Specify the resistor supervision scheme used with the auxiliary security
device.
Resistor 1 Specify the value of supervision resistor R1. 5k1
Resistor 2 Specify the value of supervision resistor R2 (available when dual resistor
supervision is selected).
Noise Tolerance
Used to compensate for noisy input wiring (0, 20, 40, 60, 80, 100 mV) when
using single/dual resistor supervision on the auxiliary input. Set this parameter
in conjunction with the Filter Window setting to reduce FAR/NAR.
40
Line Drop
Used to compensate for the voltage drop on long or high resistance input
wiring (0, 20, 40, 60 mV) available with single/dual resistor supervision.
0
Filter Window
(msec)
Specifies the time for which an input must remain active before an event is
declared (0 to 2.5 s in 125 ms increments). Adjust the Filter Window in
conjunction with the Noise Tolerance to reduce FAR/NAR.
250 msec
Control Activation
Alarm Specify a relay that will activate to signal an Auxiliary Input alarm condition
(Local control mode or NM Mode).
Supervision Specify a relay that will activate to signal an Auxiliary Input supervision
condition (Local control mode or NM Mode).