Installation Guide

Table Of Contents
APCC Installation Procedures
Access Points Controller Card (APCC) 19
Sensys Networks, Inc. Installation Guide
NOTE:
After the cabinet backplane is queried for an address, be sure to take the APCC card out of
X-mode by setting front-panel dip switch 2 to the right, and resetting the card.
Setting the Slot-Number With Circuit-board Dip Switch SW2
Circuit-board dip switch SW2 implements the slot number component of the Card
ID. Set switch SW2 to match the value derived from the figure in Appendix A
subject to the exception noted below.
Exception
In cases where the controller does not assign an address, the installer will see a
front-panel channel LED display pattern indicating an address of 15 (all LEDs
lighted). This address can be used for the first contact closure card installed.
However, subsequent cards must be given a different address – arbitrarily
assigned by the installer. Any value between 0 and 15 may be used; remember that
Card IDs must be unique for the network.
Refer to
Appendix C: Circuit-board Dip Switch SW2 Settings for a figure that illustrates
how to set switch SW2 to values between 0 and 15.
Setting the Shelf-Number With Circuit-board Dip Switch SW1
Circuit-board dip switch SW1 implements the shelf number component of the
Card ID. Shelf numbers are assigned by the installer after visually inspecting the
cabinet.
The convention is to consider the top-most shelf in the card rack as shelf zero and
to increment the shelf number by one for each shelf below the top-most shelf. For
example, the bottom shelf in a cabinet of four shelves would be considered shelf
three.
Set circuit-board dip switch SW1 to the shelf number using the two left-most
switches. Refer to
Appendix B: Circuit-board Dip Switch SW1 Settings for a figure that
illustrates how to set switch SW1 to values between 0 and 3.
Determining the Controller Type and Setting it via Circuit-
board Dip Switch SW1
At the factory, contact closure cards are set for use with Type 170, Type 2070
(without status relays), or NEMA TS1 traffic controllers. This setting is made with
switch three of circuit-board dip switch SW1.
Verify the controller type and set dip three of circuit-board dip switch SW1 as
needed. Use the figure in
Appendix B: Circuit-board Dip Switch SW1 Settings as a guide
for setting switch three of SW1 to the proper value.