Instruction Manual
COMPUTER
ROOM
OUTSIDE
WALL OR WINDOW
TOO HOT/COLD
INSIDE WALL
TOO HOT/COLD
COPIER
TOO NEAR
EQUIPMENT OR DOORWAY
GOOD
LOCATION
GOOD
LOCATION
GOOD
LOCATION
INSTALLATION
1. IMPORTANT! Locate the device in an area away from
ventilation sources and heat generating equipment and
appliances. The device should be mounted at light switch
height in a vertical orientation. Use insulating material behind
the device to ensure reading accuracy.
NOTE: Do not install the device in multi-gang electrical boxes
with line voltage or other electrical devices.
2. Wire according to application. See “Setup- Wiring” section for
details.
3. Install backplate to wall or junction-box using screws
provided. If using optional trim ring, click the TotalSense into
it and secure using 1 screw. Then, mount it to wall or junction
box.
4. Apply power.
5. To congure communications or analog voltage scaling,
congure DIP switches according to “Setup - Analog” or "setup -
Communications" sections.
To congure the device using the color OLED screen, reference
the “Setup - Display” section.
SETUP - WIRING
The following diagrams show terminal locations for each
version of the TotalSense. The number of options selected will
determine which of the terminals are included on each device.
For example, if only one sensor is chosen, only 1 pair of analog
terminals will be present. Each device will have 4-8 terminals
on the left side, 0-4 on the top, and 0-4 on the right side.
Analog Wiring
*These terminals may not be populated depending on which
model is ordered.
Communications Wiring
NOTE: A 120 termination resistance may be added in parallel
with the RS-485 +/- by moving the very top DIP switch (DIP 1)
to the left position. See “DIP Conguration” section for more
information.
SETUP - ANALOG
Switch 1 with two DIP switches will be provided with every
device and Switch 2 with an additional 12 DIP switches will be
provided with communications devices. The following diagram
shows how each setting can be congured using the provided
switches.
For analog voltage output, select either 0-5V (left) or 0-10V
(right) outputs. These analog ranges can be adjusted using
the color OLED display. Adjustments made using the OLED
display will override this DIP switch setting.
DIP
1
2
Left
0-5V
N/A
Right
0-10V
N/A
Analog DIP Settings
S1
ON
RELAY* THERMISTOR*
BUTTON* SLIDER*
PWR
O1O2
GND
O6 O5 O4 O3
O2
RELAY* THERMISTOR*
BUTTON* SLIDER*
PWR
O1
GND
O3
*BUTTON *SLIDER
S1
PWR
02 O1
GND
O6 O5
O4 O3
S1
*RELAY *THERMISTOR
PWR
02 O1
GND
O3
*BUTTON *SLIDER
S1
S3
S3
S1
nalog T
*BUTTON *SLIDER
S1
PWR
02 O1
GND
O6 O5
O4 O3
S1
*RELAY *THERMISTOR
Page 2 of 6
DIMENSIONS
A concealment ring is provided to
hide oversized cutouts or to mount
using a European sized junction box.
6.35
[161.3]
3.69
[93.7]
3.00
[76.2]
1.07
[27.1]
1.25
[31.6]
0.229
[35.8]
5.66
[143.8]