Instruction Manual
SETUP - COMMUNICATIONS
DIP
1
2
Left
N/A
Modbus
Right
Termination Resistor
BACnet
Comms DIP Settings
Left
0 (off)
0
0
0
0
0
0
0
0
0
0
0
DIP
1
2
3
4
5
6
7
8
9
10
11
12
Function
MAC6
MAC5
MAC4
MAC3
MAC2
MAC1
MAC0
BAUD2
BAUD1
BAUD0
D/P/S1
D/P/S0
Right
1 (on)
1
1
1
1
1
1
1
1
1
1
1
DIP
1-7
8-10
11-12
Function
MAC Address/
Modbus Address
0-127 (binary)
Baud Rate
0(000)=9600
1(001)=19200
2(010)=38400
3(011)=57600
4(100)=76800
5(101)=115200
Data/Parity/Stp
0(00)=8N1
1(01)=8N2
2(10)=8O1
3(11)=8E1
S1
S3
ON
ON
1 2
1 2 3 4 5 6 7 8 9 10 11 12
DIP switches 1-7 can be arranged in 127 binary congurations
to set the MAC address (BACnet) or the Modbus address.
Similarly, the baud rate can be set by DIP switches 8-10 and the
data/parity/stop bit can be set by DIP switches 11 and 12.
ADVANCED SETUP
Display Navigation
Guide
BACnet Protocol
Guide
PWR
02 O1
GND
O3
*BUTTON *SLIDER
S1
S3
S3
S1
SETUP - DISPLAY
Example screen:
TotalSense devices ordered with color OLED display can
be congured from the display or over communications (if
applicable). The default screen layout will vary depending
on which model is ordered. Each of the 5 sections can
be customized. See “Display Navigation Guide” for more
information.
Set Point
o
F
72
o
F
72
%RH
45
Good
Air Quality
425
PPM
Screen Lock:
If the screen is locked, a lock icon will show when any button
is pressed. To unlock, hold the UP and DOWN arrows for 5
seconds. To disable the lock feature, see “Display Navigation
Guide”.
Fair
Air Quality
Screen saver
(locked)
o
F
%RH
45 72
Fair
Air Quality
Home Screen
(unlocked)
5 seconds
V
V
To unlock To settings
Changing Settings:
To change any setting, press ENTER to see the setup menu and
navigate to the desired parameter type and press ENTER again
to choose. The example below shows how to adjust the center
reading on the display. The dashed blue line shows the desired
selections and the blue buttons show how to navigate.
Changing a value:
To adjust a numerical setting, set each digit individually and
press ENTER to move the cursor from left to right. When all
digits are set, the value will be saved when ENTER is pressed
again.
Centern/Off
Noner Quality
Upper
Relayint
Upper
Slider
RH
Range Max
Min 0
199 %
Max 100
Centern/Off
Noner Quality
Upper
Relayint
Upper
Slider
RH
Range Max
Min 0
099 %
Max 100
Centern/Off
Noner Quality
Upper
Relayint
Upper
Slider
RH
Range Max
Min 0
109 %
Max 100
Save
Digit
Save
Digit
Save
Entry
Modbus Protocol
Guide
Page 3 of 6
Go Back
Display
Analog Output 1
Analog Output 2
Analog Output 3
Settings
Go Back
Center Display
None
Upper Left
Relay State
Display
Home
Settings
View Comms
View Readings
Administration
Main Menu
V V V
Centern/Off
Noner Quality
Upper
Relayint
Upper
Slider
Display
Center
None
Temp
RH
CO2
Centern/Off
Noner Quality
Upper
Relayint
Upper
Slider
Display
Center
Air Quality
TVOC PPB
TVOC ug/m3
PM
Go Back
Center Display
Air Quality
Upper Left
Relay State
Display
x 4
V
V
Save