Specifications

118 Advanced Operations
Installation and Operations Manual
Displaying Syslog configuration information:
The Show Syslog command displays Syslog configuration information.
To display the Syslog configuration information:
At the Switched CDU: prompt, type show syslog and press Enter.
Example
The following command displays the Syslog configuration information:
Switched CDU: show syslog<Enter>
SYSLOG Configuration
Primary Host: 10.1.2.80
Secondary Host:
Port: 514
Email
Email Command Summary
Command Description
Set Email Enables or disables Email notification support
Set Email Auth Enables or disables notification of all authentication attempts
Set Email Config Enables or disables notification of configuration changes
Set Email Event Enables or disables notification of general system events
Set Email From Sets the email ‘From’ address
Set Email Power Enables or disables notification of power state change requests
Set Email PrimaryTo Sets the primary recipient email address
Set Email SecondaryTo Sets the secondary recipient email address
Set Email Test Sends a test email to the target email destinations
Set Email SMTP Port Sets the SMTP server port number
Set Email SMTP AuthType Determines the SMTP authentication type
Set Email SMTP Host Sets the SMTP Host IP address or hostname
Set Email SMTP Password Sets the password for SMTP authentication with username
Set Email SMTP Use ‘From’ Address Uses the SMTP ‘From” address for SMTP authentication
Set Email SMTP Username Sets the username for SMTP authentication
Set Email SMTP Useusername Uses the SMTP username/password for SMTP authentication
Show Email Displays all Email configuration information
Enabling or disabling Email notification Support:
The Set Email command enables or disables Email notification support.
To enable or disable Email notification support:
At the Switched CDU: prompt, type set email, followed by enabled or disabled and press Enter.
Setting the SMTP server address:
The Set Email Host command sets the IP address or hostname of the SMTP server.
NOTE: Both IPv4 and IPv6 formats are accepted for IP address or hostname.
To set the SMTP server address:
At the Switched CDU: prompt, type set email smtp host, followed by the SMTP server’s IP address or
hostname and press Enter.
Examples
The following command sets the SMTP server address to 55.55.55.55:
Switched CDU: set email smtp 55.55.55.55<Enter>
The following command sets the SMTP server address to email.servertech.com:
Switched CDU: set email smtp email.servertech.com<Enter>