Specifications

High Limit: Displays the high limit of the load, temperature, or humidity graph. These values depend
on the sensor limits are cannot be set by the user. For example, a 100ºC high limit would be displayed
as
for a temperature sensor graph in Celsius.
Status: One of several operating conditions:
System Summary – Status Descriptions
Icon Status Description
Reading Unit is reading a new or restored sensor.
Normal Indicates normal operation.
Load High Infeed current load exceeds present High threshold.
Over Load Infeed current load exceeds the measurable range for the infeed.
Temp Low Current temperature falls below present Low threshold.
Temp High Current temperature exceeds present High threshold.
Humid Low Current percentage of relative humidity falls below present Low threshold.
Humid High Current percentage of relative humidity exceeds present High threshold.
Lost The connection was lost to a sensor that was previously detected and the sensor is
pulled from the original environment monitoring statistics. There is no data to report,
the graph is meaningless, and the threshold settings remain displayed but are grayed.
Sensor Graph Color-Coding
The following colors change dynamically on the sensor graphs to communicate operating conditions:
Line (Load) Status:
Green = Normal
Yellow = High load (load configured by user)
Red = Overload (based on device characteristics)
User configures load capacity at Configuration > SNMP/Thresholds > Input Feed Traps and
Thresholds
Temperature Status:
Blue = cold; low temperature (threshold configured by user)
Green = acceptable temperature range
Red = hot; high temperature (threshold configured by user)
User configures low/high temperature thresholds at Configuration > SNMP/Thresholds > Sensor
Traps and Thresholds
Humidity Status:
Blue = wet; high humidity (threshold configured by user)
Green = acceptable percentage of relative humidity
Yellow = dry; low humidity (threshold configured by user)
User configures low/high relative humidity thresholds at Configuration > SNMP/Thresholds >
Sensor Traps and Thresholds
Operations 19