Specifications

30 Operations
Installation and Operations Manual
Editing the UPS SNMP GET community string:
In the SNMP GET Community String field, type the community string configured on the UPS device
and click Apply.
Enabling/Disabling UPS voltage polling:
From the Poll UPS Voltage drop-down list, select Enabled or Disabled and click Apply.
Editing the UPS SNMP port number:
In the Port field, type the port number and click Apply.
Associate the UPS with an infeed:
Select the infeed(s) powered by the UPS and click Apply.
To remove a UPS:
On the Configuration UPS page, under the Action heading, click the Remove link for the UPS you
want to remove.
Outlets
The Outlets configuration page allows you to assign and edit outlet sequence/reboot timers, descriptive
names, and wakeup states.
Setting the outlet sequencing interval:
Enter the sequencing interval (in seconds) in the Sequence Interval field and click Apply.
Setting the outlet reboot delay:
Enter the reboot interval (in seconds) in the Reboot Delay field and click Apply.
Editing the outlet descriptive name:
Click on the Edit link in the Action column next to the outlet to be configured.
On the subsequent Outlet Edit page, enter a descriptive name. Up to 24 alphanumeric and other typed
characters (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Press Apply.
Changing the outlet wakeup state:
Click on the Edit link in the Action column next to the outlet to be configured.
On the subsequent Outlet Edit page, select On, Off or Last from the Wakeup State drop-down menu
and click Apply.
Setting the outlet Post-On delay:
Click on the Edit link in the Action column next to the outlet to be configured.
On the subsequent Outlet Edit page, enter the outlet Post-On delay (in seconds) in the Post-On Delay
field and click Apply.
Groups
The Groups configuration page is used for creation and deletion of group and assignment of outlets to
groups.
Creating a group:
Enter a descriptive group name in the Group Name field. Up to 24 alphanumeric and other typed
characters (ASCII 33 to 126 decimal) are allowed; spaces are not allowed. Click Apply.
Removing a group:
Click on the Remove link in the Action column for the group to be removed and click Yes on the
subsequent confirmation window.
Adding and Deleting outlets from a group:
Click the Edit link in the Action column for the associated group.
On the subsequent Group Edit page, select or deselect outlets to be included in that group. Click
Apply.