Specifications

46 Operations
Installation and Operations Manual
Rebooting outlets:
The Reboot command reboots one or more outlets. This operation turns the outlet(s) off, delays for a
user configurable period and then turns the outlet(s) on. When the command completes, a display
indicating all outlets affected and their current states will be displayed.
NOTE: You will need to re-issue the Status command to verify that the outlets have rebooted.
To reboot one or more outlets:
At the Switched CDU: prompt, type reboot, followed by an outlet name, and press Enter, or
Type reboot, followed by a group name, and press Enter, or
Type reboot all and press Enter.
Example
The following command reboots all the outlets in the group named ServerGroup_1:
Switched CDU: reboot ServerGroup_1<Enter>
Displaying outlet status:
The Status command displays the on/off status of one or more outlets. The command displays the status of
only those outlets for which the current username has power control access.
This display includes the outlet absolute and descriptive names, the Outlet State reported to the unit by
the outlet and the current control state being applied by the PT22. If you do not specify any parameter
with this command, the status of all accessible outlets is displayed.
NOTE: If the user has access to more than 16 total outlets, the Status command will display the first 16 outlets with a
prompt to view the remaining outlets.
To display on/off status of one or more outlets:
At the Switched CDU: prompt, type status, followed by an outlet name, and press Enter, or
Type status, followed by a group name, and press Enter, or
Type status and press Enter.
Examples
The following command displays the on/off status of the outlet named FileServer_1:
Switched CDU: status FileServer_1<Enter>
Outlet Outlet Outlet Control
ID Name State State
.C1 FileServer_1 On On
The following command displays the on/off status of all accessible outlets:
Switched CDU: status<Enter>
Outlet Outlet Outlet Control
ID Name State State
.A1 DataServer_1 On On
.B1 WebServer_1 On On
.C1 FileServer_1 On On
.D1 On On
The following command displays the on/off status for outlets in the group ServerGroup_1:
Switched CDU: status ServerGroup_1<Enter>
Group: ServerGroup_1
Outlet Outlet Outlet Control
ID Name State State
.A1 DataServer_1 On On
.B1 WebServer_1 On On
.C1 FileServer_1 On On