Specifications

62 Operations
Installation and Operations Manual
Setting the system 3-phase load out-of-balance threshold:
The Set System Balance command is used to set the percentage out-of-balance threshold for loads on 3-
phase input voltage devices.
To set the system 3-phase load out-of-balance threshold:
At the Switched CDU: prompt, type set system balance, followed a value from 0 to 100 (in
percentage) and press Enter.
Example
The following command sets the system 3-phase load out-of-balance threshold to 20 percent:
Switched CDU: set system balance 20<Enter>
Displaying system configuration information:
The Show System command displays all system configuration information.
Firmware version
NIC module serial number and MAC address
Hardware revision code and Flash size
Uptime since last system restart
System location description
To display system configuration information:
At the Switched CDU: prompt, type show system and press Enter.
Example
System Information
F/W Version: Sentry Switched CDU Version 7.0d
NIC S/N: 8217984
MAC Address: 00-0a-9c-10-00-01
H/W Rev Code: 64 (NIM)
Flash Size: 2 MB
Uptime: 4 days 22 hours 0 minutes 3 seconds
Location: Bldg-1
Area <Footprint>: 4.5 square feet
Power Factor: 0.88
3-Phase Load
Out-of-Balance
Threshold: 20 percent
Displaying system power status:
The System Status command displays all power status information.
To display system power status:
At the Switched CDU: prompt, type sysstat and press Enter.
Example
Switched CDU: sysstat
System Power Status
Area <Footprint>: 100.0 Square Meters
Watts Per Area Unit: 2 Watts Per Square Meter