Specifications

Operations 77
Installation and Operations Manual
Removing a UPS record:
The Remove UPS command removes a UPS record.
To remove a UPS record:
At the Switched CDU: prompt, type remove ups and press Enter.
At the prompt, type the index number of the UPS to be removed and press Enter.
Example
The following command removes the UPS record at index 3:
Switched CDU: remove ups<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: Powerware
Host/IP: DC1Powerware1
3 Type: Toshiba
Host/IP: DC1Toshiba1
Select UPS(1-8): 3<Enter>
Changing the UPS type:
The Set UPS Type command is used to change the type of UPS for each UPS record.
To change a UPS record:
At the Switched CDU: prompt, type set ups type and press Enter.
At the prompt, type the index number for the UPS record to be changed and press Enter.
At the prompt, type the corresponding number from the list of the UPS types and press Enter.
Example
The following command changes port for the UPS record at index number 1 to ‘162’:
Switched CDU: set ups port<Enter>
UPS UPS
Index Type Port
1 Liebert 161
2 MGE 161
Select UPS(1-8): 1<Enter>
Port: 162<Enter>
Changing the UPS host address:
The Set UPS Host command is used to change the IP address or hostname for each UPS record.
Hostnames can be up to 60 characters long.
To change a UPS host address:
At the Switched CDU: prompt, type set ups host and press Enter.
At the prompt, type the index number for the UPS record to be changed and press Enter.
At the prompt, type IP address or hostname for the UPS and press Enter.
Example
The following command changes UPS hostname for the record at index number 2 to ‘DC1MGE1’:
Switched CDU: set ups host<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: MGE
Host/IP: DC1Powerware1
Select UPS(1-8): 2<Enter>
Host/IP: DC1MGE1<Enter>