Specifications

94 Advanced Operations
Installation and Operations Manual
Setting the Infeed Load limit:
The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.
To set the infeed load limit:
At the Switched CDU: prompt, type set trap infeed loadhigh, followed by the infeed name, and a
value from 0 to 255 in amperes. Press Enter.
Example
The following command sets the infeed load limit for the second infeed on the first tower to 25
amperes, using the absolute name of the infeed:
Switched CDU: set trap infeed loadhigh .ab 25<Enter>
Enabling or Disabling a Change trap:
The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the Switched CDU: prompt, type set trap outlet change, followed by the outlet name and on or off. Press
Enter, or
Type set trap outlet change all, followed by on or off and press Enter.
Example
The following command enables the Change trap for the third outlet on the first infeed of the second
tower, using the outlet’s absolute name:
Switched CDU: set trap outlet change .ba3 on<Enter>
Enabling or Disabling the Temp trap:
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the Switched CDU: prompt, type set trap ths temp, followed by the sensor name and on or off.
Press Enter.
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
Switched CDU: set trap ths temp .a1 on<Enter>
Setting the Temperature sensor threshold limits:
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and
upper threshold limits for the Temperature sensor.
To set the Temperature threshold limits:
At the Switched CDU: prompt, type set trap ths, templow or temphigh, followed by the sensor name
and a value from 0 to 123 in degrees Celsius. Press Enter.
Example
The following command sets the second temperature high threshold limit to 95:
Switched CDU: set trap ths temphigh .a2 95<Enter>