Instruction Manual

Setra Systems Model 201
Pressure Transducers
1.0 GENERAL INFORMATION
Every Model 201 has been tested and calibrated before shipment. Specific
performance specifications are shown on page 3 of this Guide.
Setra Systems 201 pressure transducers sense gauge and differential pressure and
convert this pressure difference to a proportional high level analog output. The
Model 201 is a 4 to 20 MA output device.
2.0 MECHANICAL INSTALLATION
2.1 Media Compatibility
Model 201 transducers are designed to be used with any gases or liquids
compatible with 316 Stainless Steel and Inconel® in process port. Reference port
must be exposed to clean dry air or non-corrosive gas.
2.2 Environment
The operating temperature limits of the 201 are -40° to +175°F (-40 to
+80°C). The compensated temperature range is -25 to +175°F (-33 to +80°C).
2.3 Pressure Fittings
Typically, standard pipe fittings and procedures should be used. Excessive torquing
of metal fittings may cause a slight zero shift. The use of plastic fittings typically
results in no noticeable zero shift. Torquing does not appreciably affect linearity or
sensitivity.
2.4 Venting for Gauge Pressure Measurements
All 201 units are vented to atmosphere through a Barbed reference port at the
bottom of the unit.
2.5 Differential Pressure Measurements
Connect low pressure tube to reference port. Note: Media into reference port must be
clean dry air or non-corrosive gas.
Installation Guide
CONDUIT
FITTING
1/2 NPT
7/8 HEX
1/4 - 18 NPT MALE
1.96
50
POSITIVE PRESSURE
PROCESS PORT
5.41
137
2.00 DIA
50 DIA
REFERENCE PORT
BARBED FITTING
FOR Flexible 1/4” ID
TUBE
CONNECTION