4.7 SETUP ALARMS SCREEN
From this screen the user can access the following:
a.  Latched Alarm requires the pressure to return to normal and the
  alarm to be acknowledged before the alarm can be silenced and
  reset.
b.  Enable the audible alarm by selecting “Yes” or use visual only alarm 
by selecting “No”. 
c.  Provide a “door open” warning visual indication. When a door jamb
  contact switch is used and this button is activated by pressing “Yes”, 
the door status “open” condition is indicated by the touch screen 
display turning from green to yellow, and door open indicated on the 
monitoring (default) screen.
d.  Set the time (in seconds) that the alarm can be silenced in the 
latched alarm mode before the alarm resumes. This assumes that 
the room static pressure is still outside the normal or set operating 
limits. The Mute Time Out can be set from 0 to 9999 seconds.
e.  Set the Alarm Delay (in seconds) from the time that the room 
pressure goes out of the preset limits until the alarm activates. The 
alarm delay may be set from 0 to 9999 seconds.
f.  Set the alarm volume or sound level. Using the Up and Down keys, 
the volume can be set at level 1-4. Level 4 alarm volume is the 
loudest and corresponds to a sound level of 85 dB at a distance of 4 
inches.
ALARM SETUP OPERATION
Lightly press (or tap) button to select “Yes” or “No” for Latch Alarm, 
Audible Alarm, or Door Alarm Inputs. Selected box background will 
change from clear to black when selected.
MUTE TIME OUT/ALARM DELAY
Pressing (or tapping) the “Mute Time Out” or “Alarm Delay” box activates 
the Data Entry screen to set the time delay duration.