3.0 INSTALLATION (See Section 8.0 for overview)
The SRPM is designed to be mounted on a standard double gang  metal 
electrical  box  using  a  4  x  4  inch  plaster  ring  adaptor. After  the rough in 
wiring and plumbing is performed remove the cover and mount the baseplate 
to the plaster ring adaptor using the supplied 6-32 x 1/2” long mounting 
screws. Note: The plaster ring external mounting face needs to be positioned 
fl ush to recessed, relative to the surface of the wall. Also note the orientation 
of the 4 mounting screws in the plaster ring, as the plaster ring is rotated 
90° from conventional mounting.
Note: In the following wiring sections, abbreviations are used (e.g. J1, P3). 
Please see section 8.0 for complete wiring diagrams with abbreviations.
3.1 WIRING ELECTRICAL BOX (ROUGH IN)
Layout  the  system  in  terms  of  wiring:  power,  annunciator,  analog  output, 
BACnet,  relay  output  and  plumbing  to  connect  to  the  monitored  spaces 
(pressure taps).
Bring all power, earth ground, signal, communications and analog output 
wiring into the 4x4 electrical box. 
Bring 1/4” O.D. tubing for 3/6” Barb fi tting into box.
In order to conform to the CSA safety standard the electrical installer must 
comply  with  the  following  earth  ground instructions.  Pre-wire  the electrical 
box with power (24 VAC or 120/240), and provide earth grounding to the 
electrical box. The safety ground path consists of  four  6-32 x 1/2”  metal 
screws that connect the SRPM metal base to the 4½ x 4½ metal plaster 
ring. The plaster ring must be grounded to the 4½ x 4½ electrical box by 2 
metal mounting screws. The 4½ x 4½ electrical box must be connected  to 
the building earth ground. It is also highly recommended to use armored 
cable (Type AC) for all the wiring in applications where high levels of radio 
interference may be present.
Electrical Box
4 x 4 inch Plaster Ring 
4 x 4 inch Plaster Ring 
4 x 4 inch Plaster Ring 
(Rotated 90°)
(Rotated 90°)
SRPM Metal Base
SRPM Metal Base
SRPM Cover
For 120/240 VAC Version, only
CAUTION: 
Do not open or remove SRPM cover (tool required) with input power ap-
plied unless performed by a licensed electrician. “Hazardous Live” voltage is present at 
connector J3 when power is applied. Please observe the warning symbol ( ) near the 
J3 power connector.
!
connector J3 when power is applied. Please observe the warning symbol ( ) near the 
connector J3 when power is applied. Please observe the warning symbol ( ) near the 
connector J3 when power is applied. Please observe the warning symbol ( ) near the 
!