Communication channel
4-0, channel (862M + CHAN*1M), default 06H868MHz
00H-45H, correspond to 862~931MHz
Fixed transmission enabling bitsimilar to MODBUS
In fixed transmission mode, the first three
bytes of each user's data frame can be used
as high/low address and channel. The
module changes its address and channel
when transmit. And it will revert to
original setting after complete the process.
Transparent transmission mode
Fixed transmission mode
OPTI
ON
IO drive mode (default 1)
This bit is used to the module internal
pull-up resistor. It also increases the
level’s adaptability in case of open drain.
But in some cases, it may need external
pull-up resistor.
TXD and AUX push-pull outputs, RXD pull-up inputs
TXDAUX open-collector outputs, RXD open-collector
inputs
Shanghai Smart Control Co., Ltd.
16
Low address byte of module
ADDL
the default 00H
00H-FFH
UART parity bit
8N1 (default)
UART mode can be different between
communication parties
8O1
8 E1
8N1 (equal to 00)
TTL UART baud ratebps
1200
2400
UART baud rate can be different between
communication parties
4800
The UART baud rate has nothing to do
with wireless transmission parameters &
won’t affect the wireless transmit / receive
features.
9600 (default)
19200
38400
SPED
57600
115200
Air data ratebps
0.3k
The lower the air data rate, the longer the
1.2k
transmitting
distance,
better
2.4k (default)
4.8k
anti-interference performance and longer
transmitting time
9.6k
The air data rate must keep the same for
both communication parties.
19.2k
19.2k (same to 101)
19.2k (same to 101)
General Specifications
reserved
Write 0