Install Instructions
11
MAKING A SHARKBITE
®
UNIVERSAL CONNECTION
Installation Requirements
SharkBite Fitting Reuse
SharkBite Universal fittings are intended to be a
permanent connection and are not designed for
repeated connection and disconnection. If the need
arises to change a fitting after initial installation this can
be done given that proper care is taken when removing
and reinstalling SharkBite Universal fittings.
SharkBite disconnect tongs or SharkBite disconnect clips
must be used when removing the fittings.
The initial pipe and the new pipe must be clean and free
from scratches and burrs.
Mark the correct insertion depth, insert the fitting to the
mark, turn the water back on and check for leaks.
Working Pressure and Temperature
SharkBite Universal fittings have a maximum
temperature of 200°F maximum pressure 200 psi when
used on copper pipe. When used on PVC, CPVC, PEX, PE-
RT or HDPE refer to the maximum pressure temperature
rating of the pipe.
PEX Stieners
SharkBite Universal fittings (3/8" to 1") come with an
Integral PEX Stiener. 1/4" (3/8" OD) fittings do not
require PEX stieners. PEX Stiener are required for
PEX, PE-RT and HDPE pipe. 2XL PEX Stieners sold
separately.
Pressure Testing EvoPEX Systems:
Always refer to local code for pressure testing EvoPEX
systems after installation. Testing must be completed prior to
concealing fittings with concrete or by other means. Only use
dishwashing liquid soap and water to detect plumbing leaks.
Avoid using 'Leak Detector' spray products.
Water Testing:
When water is used for pressure testing and the building
is unheated, the system should be drained after testing to
prevent freezing. The test pressure applied to the system
must meet the pressure testing requirements of local code,
but cannot be lower than the system operating pressure. The
pressure with water cannot exceed the following pipe listings:
73.4F (23C) at 160psi
180F (82.2C) at 100psi
200F (93.3C) at 80psi
It is recommended to test at a pressure of 80psi (unless local
code indicates higher pressures). The test duration should
not be less than 15 minutes.
Air Testing:
When air is used for pressure testing pressure should be from
40 psi to 125 psi, a common test pressure is 100 psi. The
duration should be not be less than one hour and the pressure
shall not drop more than 8 psi in one hour (deformation of
the tube and slow expansion can cause the 8 psi pressure
drop). If the system pressure falls more than 8 psi in one hour
the test needs to be repeated. If the problem continues use
a soapy solution to detect the faulty connection, replace the
connection and repeat the test.