Parameter name Parameter description Setting
range
Default
setting
S5.16 INVERTED OUTPUT FOR
SWITCHOVER BETWEEN
HEAT SOURCES
By schemes with two heat sources it can be set if output
for switchover between two heat sources is inverted.
0- NORMAL
1- INVERTED
0
S5.17
FLUE GASES TEMP. FOR
SWITCHOVER TO SOLID
FUEL BOILER



cases the switchover from oil boiler to solid fuel boiler is

temperature. Set also parameter S1.4=7 (for sensor T1) or
S1.5=10 (for sensor T8).
70 ÷ 350 °C
130
S5.18
MAX. FLUE GASES
TEMPERATURE

temperature exceeds setted value, controller indicates it.
Set also parameter S1.4=7 (for sensor T1) or S1.5=10 (for
sensor T8).
70 ÷ 350 °C
200
S5.19
MIN. FLUE GASES TEMP.
FOR SOLID FUEL BOILER

above which the operation of liquid fuel boiler is disabled.
This option is used if the liquid and solid fuel boiler are
connected on the same chimney pipe and is prohibited to
have dual boiler operation.
Also set parameter S1.4=10 (for sensor T1) or S1.5=13 (for
sensor T8).
50 ÷ 150 °C
100
S5.20
SWITCH-OFF DIFFE-
RENCE FOR BOILER
RETURN–PIPE CONTROL
Setting of switch-off difference (between boiler and boiler
return pipe temperature) for boiler return pipe pump.
1 ÷ 20 °C
4

Para-
meter
Parameter name Parameter description Setting range Default
setting
S6.1 PROTECTION OF MAX.
COLLECTORS OR SOLID
FUEL BOILER TEMPE-
RATURE
With this setting is activated protection of max. solar coll-
ector or solid fuel boiler temperature. If solar collector or
solid fuel boiler temprature is exceeded, circulation pump
in solar system will activate although d. h. w. temperature
is already reached.
0- NO
1- YES
1
S6.2 MAX. TEMPERATURE OF
COLLECTORS OR SOLID
FUEL BOILER
Setting of maximum solar collectors or solid fuel boiler
temperature.
90 ÷ 290 °C
120
S6.3 EMERGENCY SHUT-
DOWN TEMPERATURE
FOR COLLECTORS OR
SOLID FUEL BOILER
If solar collector or solid fuel boiler emergency shutdown
temperature is exceeded, circulation pump will stop
unconditionally.
120 ÷ 350 °C
160
S6.4 COLLECTOR’S FROST
PROTECTION
If the temperature drops bellow the set point value (S6.5),
the solar pump switches -on to prevent freezing in the
collectors and pipelines.
NOTE: This setting is suitable only for climates areas
where the temperature only occasionally drops bellow the
freezing point.
0- NO
1- YES
0
S6.5 COLLECTOR’S FROST
PROTECTION TEMPE-
RATURE

protection should activate.
-20 ÷ 10 °C
4