Technical specifications
Example
Calculating the response time for a cascaded system without beam coding in which fields
a
re configured with floating blanking:
Line Required detail Response time
1 Host: 750 mm protective field height, resolution 14 mm 16 ms
2 Guest 1: 300 mm protective field height, resolution
40 mm
+ 9 ms
3
Guest 2: – + 0 ms
Greatest response time from lines
1 to 3: 16 ms × 0.5 =
+ 8 ms
4 Only if floating
blanking is used:
Deduct 4 ms here. 4 ms
5 If single guest is used, then add 8 ms here. (If no guest is
used or two guests are used, do not add anything here.) + 8 ms
6 Total response time to be taken into account = 37 ms
Number of beams for physical resolutionProtective field height
[mm]
14 mm 20 mm 30 mm 40 mm
150 20 8
300 40 30 15 10
450 60 45 23 15
600 80 60 30 20
750 100 75 38 25
900 120 90 45 30
1050 140 105 53 35
1200 160 120 60 40
1350 180 135 68 45
1500 200 150 75 50
1650 220 165 83 55
1800 240 180 90 60
Tab.
31
:
Number of beams
depending on the protective
field height and the physical
resolution