Technical data

I/O Modules 193
Configuration and Parameterization of the I/O Modules
WAGO-I/O-SYSTEM 750
Bus System
5.4.3.2 PWM Module
Module
Identification
hex
Identification
dec
750-511 0xF2 242
Process Image
Input Image
in [Byte]
Output Image
in [Byte]
Internal bus 6 6
Register communication
possible
Yes 6 6
PROFIBUS DP
No (not possible) - -
PFC (CPU) 6 6
Parameter Value Meaning
I/O module is physically The I/O module process data is
plug fitted
*)
- supplied by the I/O module or
supplied to the I/O module
not plug fitted - set to zero by the coupler or
ignored by the coupler
Substitute channel x
0x0000
*)
...
0x7FFF
If, in the case of a PROFIBUS DP fault, the
switching of substitute values is enabled by the
coupler parameterization, this data is transmitted
to the periphery in the case of a fault..
*)
Default settings
Parameter
Offset
Information
0
7 6 5 4 3 2 1 0
0 PFC Plug 0 0 0 0 0
1
7 6 5 4 3 2 1 0
1 0 1 1 1 1 0 1
2
15 14 13 12 11 9 8 7
reserved
3
7 6 5 4 3 2 1 0
reserved
4
15 14 13 12 11 9 8 7
SubVal_Ch1_HB
5
7 6 5 4 3 2 1 0
SubVal_Ch1_LB
6
15 14 13 12 11 10 9 8
SubVal_Ch2_HB
7
7 6 5 4 3 2 1 0
SubVal_Ch2_LB
PFC
6
0
1
Module is mapped in the field bus and PFC-PA
Module is exclusively mapped in the PFC-PA
Plug
5
0
1
Module is physically not present
Module is physically present (default)
SubVal_Ch1 0x0000
:
0x7FFF
Substitute channel 1
SubVal_Ch2 0x0000
:
0x7FFF
Substitute channel 2
Italic Cannot be changed