Diagnostics
Event
Solution
Input buffer full
The I/O module receives
data via the serial interface
faster than accepted by the
application.
Make sure that the application
always accepts data
immediately
Reduce data traffic
Use flow control
Reduce baud rate
Output buffer
full
The I/O module receives
data faster from the
application than it sends via
the serial interface.
Check continuous send
Reduce data traffic
Increase baud rate
Make sure that the opposite
side accepts data
Parity error
Data transmission was
interrupted.
Check the configuration of the
interface parameters
Use a shielded cable
Change wire routing
Shorten cable
Eliminate interference
Overflow
Data loss has occurred.
Reduce baud rate
9.2 Data Exchange Operating Mode
Table 41: Diagnostics, Data Exchange
Diagnostics
Event
Solution
Wrong length
The I/O modules have
different process image
sizes
Configure the same process
image size
Checksum error
Data transmission was
interrupted. The last valid
value is retained in the
process image.
Use a shielded cable
Change wire routing
Shorten cable
Eliminate interference
Timeout
The data transmission is
interrupted or has been
interrupted for a longer
period of time (see
checksum error). The
process image (input) has
been overwritten with the
value 0.
Check cable and clamping
points for uniformity
Check the configuration of the
I/O modules
for checksum error: See