DeviceNet (Master) Function
8-40
8
8-6-2 Diagnostic table
The diagnostic table that was specified in the JW-32CUM1 (control section) can be used to check the
communication status of the nodes (master and slave stations). The addresses of the diagnostic tables
(master mode: 256 bytes, slave mode: 128 bytes) are shown below.
Diagnostic data table addresses
Basic operation
mode
No. of
bytes
Fixed Free
Master Slave
OO
Master: 256
39000 to 39377 #304 to #307 *1
Slave: 128
(O: Enable) *1: Specify the top address and select enabled or disabled.
[1] When JW-32CUM1 is master mode
The diagnostic table contains a communication monitor table, an operating status monitor table, a device
status table, master status, and vender information.
1st byte (39000)
2nd byte (39001)
3rd byte (39002)
4th byte (39003)
5th byte (39004)
6th byte (39005)
7th byte (39006)
8th byte (39007)
9th byte (39010)
32nd byte (39037)
33rd byte (39040)
34th byte (39041)
35th byte (39042)
36th byte (39043)
37th byte (39044)
38th byte (39045)
39th byte (39046)
40th byte (39047)
41st byte (39050)
64th byte (39077)
65th byte (39100)
66th byte (39101)
127th byte (39176)
128th byte (39177)
129th byte (39200)
130th byte (39201)
131st byte (39202)
210th byte (39321)
211th byte (39322)
256th byte (39377)
D7 D6 D5 D4 D3 D2 D1 D0
D7 D6 D5 D4 D3 D2 D1 D0
D17 D16 D15 D14 D13 D12 D11 D10
Reserved area *3
Reserved area *3
Node 0
Node 1
Node 62
Node 63
Address *2
Bit number
Diagnostic data (256 bytes)
Master status (2 bytes)
- The error information and operating status of the master
station is indicated by turning bits ON or OFF.
- See page 8-44.
Communication monitor table (8 bytes)
- The node addresses are numbered 0 to 63.
The communication status of each node is
indicated by turning the bits ON or OFF.
ON: Normal
OFF: Abnormal
- See the next page.
-A bit representing the master station status
will turn OFF when any of the slave stations is abnormal.
Operating status monitor table (8 bytes)
- The node addresses are numbered 0 to 63.
The operating status of each node is
indicated by turning the bits ON or OFF.
ON: The slave station is operating
OFF: The slave station is idle.
- See the 8-41.
- For details about the operating status of slave stations,
see the specifications for each slave station.
Device status table (64 bytes)
- The status of the slave station devices can be monitored
by keeping track of the device status codes assigned to
each node address. 00
(H)
is normal.
- See page 8-42, 43.
76543210
15 14 13 12 11
10
98
23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24
39 38 37 36 35 34 33 32
47 46 45 44 43 42 41 40
55 54 53 52 51 50 49 48
63 62 61 60 59 58 57 56
D7 D6 D5 D4 D3 D2 D1 D0
Reserved area *3
76543210
15 14 13 12 11
10
98
23 22 21 20 19 18 17 16
31 30 29 28 27 26 25 24
39 38 37 36 35 34 33 32
47 46 45 44 43 42 41 40
55 54 53 52 51 50 49 48
63 62 61 60 59 58 57 56
Vender information (46 bytes)
- Page 8-45.
*2: Addresses in parentheses are correct when
the data table allocation system is set to
"fixed allocation."
*3: Do not change any values in the reserved
area. If you do, the JW-32CUM1 will
malfunction.