User`s manual
12-7
M-net (Master Station) Function
12
12-2-4 Parameter setting
Set the number of bytes of data to be transmitted or received between the master and slave stations
using the M-net data link.
Enter the setting in the parameter storage area.
(1) Parameter storage area
The parameter storage area in the JW-32CUM1 (master station) is "O-0 000 to 017: 16 bytes."
(2) Parameter setting details
* Enter the total number of slave stations that are connected, regardless of whether the
communication selection relay is ON or OFF.
Parameter
storage area
Setting details
O-0 000 Number of bytes transmitted from the master station (00) to slave station 01
O-0 001 Number of bytes transmitted from slave station 01 to the master station (00)
O-0 002 Number of bytes transmitted from the master station (00) to slave station 02
O-0 003 Number of bytes transmitted from slave station 02 to the master station (00)
O-0 004 Number of bytes transmitted from the master station (00) to slave station 03
O-0 005 Number of bytes transmitted from slave station 03 to the master station (00)
O-0 006 Number of bytes transmitted from the master station (00) to slave station 04
O-0 007 Number of bytes transmitted from slave station 04 to the master station (00)
O-0 010 Number of bytes transmitted from the master station (00) to slave station 05
O-0 011 Number of bytes transmitted from slave station 05 to the master station (00)
O-0 012 Number of bytes transmitted from the master station (00) to slave station 06
O-0 013 Number of bytes transmitted from slave station 06 to the master station (00)
O-0 014 Number of bytes transmitted from the master station (00) to slave station 07
O-0 015 Number of bytes transmitted from slave station 07 to the master station (00)
O-0 016 Number of slave stations connected *